Attaching The Grounding Cable - Cisco CSS11501 - 100Mbps Ethernet Load Balancing Device Hardware Installation Manual

11500 series content services switch
Hide thumbs Also See for CSS11501 - 100Mbps Ethernet Load Balancing Device:
Table of Contents

Advertisement

Connecting the Chassis to Ground

Attaching the Grounding Cable

Warning
Cisco 11500 Series Content Services Switch Hardware Installation Guide
2-24
Table 2-8
Tools and Supplies (continued)
Quantity
Description
1
Crimping tool
2
M5 screws with captive, locking
washers
The following procedure describes how to attach:
The grounding lug to the grounding cable
The grounding cable to the chassis
When you install or replace the unit, the ground connection must always be
made first and disconnected last.
Power off the chassis by setting the power switch (or switches) to the O (off)
1.
position.
Strip the covering from the end of the grounding wire
2.
amount of covering to be stripped varies depending on the type of lug you
plan to attach to the wire.
Lug
Panduit no. LCD6-10A-L
(supplied in accessory kit)
Panduit no. LCC6-10A-L
(long barrel)
Thomas & Betts no.
256-30695-1183(*4*)
Burndy no. YA6CL2TC10
Chapter 2
Cabling and Troubleshooting the CSS
Comments
Must fit diameter of grounding
lugs. Cisco Systems
recommends that you use a
crimping tool recommended by
the lug manufacturer.
Included in accessory kit
shipped with the CSS.
Strip Length
13/16 inch (2 cm)
1 1/16 inch (2.7 cm)
3/4 inch (1.9 cm)
7/8 inch (2.2 cm)
(Figure
2-10). The
78-13884-06