Honeywell FIRE-LITE MS-10UD Series Manual page 129

Fire alarm control panels
Hide thumbs Also See for FIRE-LITE MS-10UD Series:
Table of Contents

Advertisement

ANN-LED Annunciator Installation for Canadian Applications
To Remote Station Receiver
Notes:
1.
Relays 1 and 2 on the ANN-RLY must be programmed for latching alarm activation.
2.
Relays 3 and 4 on the ANN-RLY must be programmed for non-latching trouble activation.
3.
Relays 5 and 6 on the ANN-RLY must be programmed for supervisory activation with latching/non-latching set in accordance with
the local AHJ.
4.
The ANN-RLY must be mounted inside the FACP cabinet.
5.
Refer to the ANN-RLY Document #53033 for installation instructions.
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
+
ALARM
-
+
TROUBLE
-
+
SUPERVISORY
-
Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals
C
Relay 1
NC
TB2
NO
C
Relay 2
NC
TB2
NO
C
Relay 3
NC
TB4
NO
C
Relay 4
NC
TB4
NO
C
Relay 5
NC
TB5
NO
C
Relay 6
NC
TB5
NO
ANN-RLY
Canadian Applications
TB9
-
2
Non-resettable
+
1
Aux Power
FACP
129