C.1: Nfpa 72 Auxiliary Fire Alarm System - Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP30 on the MRP-2001 main circuit board to supervise placement of 4XTMF module and
circuit.
3.
Cut JP24 on the MRP-2001 main circuit board to enable FACP Supervisory relay.
4.
Refer to "4XTMF Municipal Box Transmitter Option Module" on page 31 for detailed
information.
Polarities shown in alarm condition
Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module
114
NFPA 72 Auxiliary Fire Alarm System
Municipal Box Circuit
Gamewell Model M34-56 Local
Nonpower-limited
-
+
4XTMF
MRP-2001 Series Manual — P/N 53040:H 1/26/2017