Master Programming Level
Press the number key corresponding to the desired Output Type to program the selected Output.
If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen
will be displayed:
This screen allows the programmer to select whether or not to supervise the Releasing Circuit
Output for shorts.
NOTE:
using cross-zoned inputs. Refer to "Circuit Mapping and Cross-Zoning" on page 91 for a
description of cross-zoning and input to output circuit mapping.
If Release Stage NAC is selected as the Output Type, the following subscreen will be displayed:
An NAC can be used to signal the stages of a release operation. This screen allows the programmer
to select the NAC output that will indicate the release stages for Release Circuit 1 or Release
Circuit 2. For a description of this feature, refer to "Release Stages" on page 81.

Silence

OUTPUT #
1=SILENCE
NON-SIL
2=AUTO SILENCE NO
Pressing 1 while viewing Output Screen #2 will cause the following screen to be displayed:
3=SIL INHIBITED NO
Output Screen #2
Pressing 1 while viewing the Silenceable Screen #1 will program the selected Output as a
silenceable circuit. This will allow the Output to be silenced by pressing the Alarm Silence key or
by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen #1 will program the selected Output as a
nonsilenceable circuit. This will prevent the selected main circuit board Output from being silenced
by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen #1 will program the selected Output for Stage
Silenceable. This option is used for Release Stage NACs or cross-zone coding NACs. These NACs
will be non-silenceable until its associated Release Circuit has finished discharging, after which the
NAC will become silenceable.
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
Strobe NAC
Supv Bell NAC
Trouble Bell NAC
Release Circuit 1 or Release Circuit 2
UNSUPV SHORTS - this option should normally be selected when a releasing solenoid is
connected to the output so the solenoid coil is not supervised for shorts
SUPV SHORTS - this option, which supervises for shorts, should only be selected when the
REL-4.7K option is installed in series with the solenoid coil
Release circuits may be directly activated by a single input zone or may be activated
Release Stage NAC
SILENCEABLE
1=SILENCEABLE
2=NON SILENCEABLE
3=STAGE SILENCEABLE
Silenceable Screen #1
EDIT RELEASE CIR #
1=UNSUPV SHORTS
2=SUPV SHORTS
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY
SILENCEABLE
1=SYNC MUTE
Silenceable Screen #2
Programming
57