4: Cross Input Zones; 5: On-Board Relays - Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Programming
3.5.4 Cross Input Zones
An application may require that two or more input zones become active at the same time before a
PROGRAMMING
1=CROSS INPUT ZONES
particular releasing output activates. This is referred to as cross-zoning. For example, an installer
2=ON-BOARD RELAYS
3=SYSTEM SETUP
may want four particular zones to become active at the same time before a releasing circuit is
Programming Screen #2
activated. By using the Cross Input Zone feature, the programmer can designate the input zones
that must become active and the output circuits that will be affected. Refer to "Circuit Mapping and
Cross-Zoning" on page 91 for additional information.
The Cross Input Zone option allows the user to view and program the groups of input zones that
will be used to activate one of the releasing output circuits. Pressing 1 while viewing Programming
Screen #2 will display a screen similar to the following:
This screen allows the programmer to view the cross-zoned grouping for Release Circuit 1 or
Release Circuit 2. In the following example, Template 7 has been chosen as the FACP
Configuration [refer to"FACP CONFIG (Application Templates)" on page 51]. Pressing 1 for
Release 1 Groups will display the following screen:
The display indicates that Input Zone 1 is cross-zoned with Input Zone 2. Input Zone 3 is not cross-
zoned.
The user can alter the cross-zoning by pressing the number key corresponding to the Zone to be
reprogrammed. Screens similar to the following will be displayed:
In this example, since the cross-zoning for Release Circuit 1 (Zone 1) is being displayed, Yes is
shown for Zone 1 which is cross-zoned with Zone 2. Zone 2 displays Yes since it is cross-zoned
with Zone 1. The remaining zones display NO or N/A for no cross-zoning to Zone 1. By pressing
the number key corresponding to the desired zone, the display for that zone will toggle between Yes
and No indicating cross-zoning to Zone 1 or no cross-zoning to Zone 1.
3.5.5 On-Board Relays
Pressing 2 while viewing Programming Screen #2 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:
60
CROSS INPUT ZONES
1=RELEASE 1 GROUPS
2=RELEASE 2 GROUPS
REL 1 CROSS GROUPS
1=
2=
3=
REL 1 CROSS GROUP 1
1=ZONE 1
YES
2=ZONE 2
YES
3=ZONE 3
NO
Select Cross Zone Screen #1
ON-BOARD RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
Master Programming Level
X 1 2
NONE
NONE
REL 1 CROSS GROUP 1
1=ZONE 4
NO
2=ZONE 5
NO
3=ZONE 6
N/A
Select Cross Zone Screen #2
ALARM
TROUBLE
SUPERVSRY
MRP-2001 Series Manual — P/N 53040:H 1/26/2017