Power supply unit
Power supply unit
Wattage
Rated Voltage Range
Rated Line Frequency
Rated Input Current
Heat dissipation (Configuration and software dependent)
Environmental
Temperature
Runs in the temperature Class/Severity A2 limits (18-27 °C) per
ANSI/ISA-S71.01-1985 Standard*
Operating
10 °C to 35 °C (50 °F to 95 °F)
Storage
-40 °C to +65 °C (-40°F to 149 °F)
Relative humidity
Runs in the humidity Class/Severity A2 limits (20-80%) per
ANSI/ISA-S71.01-1985 Standard*
Humidity Operating 20 % to 80 % RH, non-condensing
Maximum Altitude
15.2 m to 3,048 m (-50 ft to 10,000 ft)
Operating
Non-operating
15.2 m to 10,668 m, (-50 ft to 35,000 ft)
Airborne
< 300 angstroms/month Copper Reactivity Level
contaminant level
< 3 mm
< 10 mm
< 1 mm
< 50 mm
< 1 mm
< 500 mm
< 2 mm
Severity level G1 mild environment limits per ANSI/ISA-S71.04-
1985 Standard**
Maximum
3
3
/m
parts per billion H
3
3
/m
parts per billion S0
3
3
/m
parts per billion CI
3
3
/m
parts per billion NO
3
3
/m
parts per billion HF Gas concentration
3
3
/m
parts per billion NH
3
3
/m
parts per billion O
- 15 -
Chapter 2 - Planning
Specifications
685 W
100–240 VAC
50–60 Hz
100-240 V @ 9.7 A
Maximum – 2750 btu/hr
S Gas concentration
2
, S0
Gas concentration
2
3
Gas concentration
2
Gas concentration
X
Gas concentration
3
Gas concentration
3