Plog Transducer Rge; Plog Ref Press; Plog Cal Zero; 1 Prev Plog Cal Zero - Honeywell Mini-AT User Manual

High performance, ptz electronic volume corrector
Table of Contents

Advertisement

Item
No.
Item Name
————————————————————————————————————————
412
PLOG TRANSDUCER RGE The upper range limit of the PLog pressure transducer, always
413
PLOG REF PRESS #1The PLog pressure value used during the most recent PLog
414

PLOG CAL ZERO

415

1 PREV PLOG CAL ZERO

416
PLOG REF PRESS #2The PLog pressure value used during the most recent PLog
417
PLOG CAL SPAN
418
1 PREV PLOG CAL SPAN The previous value of item 417, updated on each PLog
419
PLOG XDCR RANGE
420
PLOG GAS PRESSURE
www.honeywell.com
134
Mini-AT User Guide
Description
expressed in PSI.
Default = 100.00
ZERO calibration.
Default = 0.00
The most recent offset value for the PLog pressure transducer,
obtained during a PLog Zero calibration. The value is
normally very close to 0.0000 and is recalculated during each
PLog Pressure Zero calibration.
Default = 0.0000
The previous value of item 414, updated on each PLog
Pressure Zero Calibration.
Default = 0.0000
SPAN calibration.
Default = 0.00
The most recent span value for the PLog pressure transducer
obtained during a PLog Span calibration. The value is
normally very close to 1.0000 and is recalculated during each
PLog Pressure Span Calibration.
Default = 1.0000
Pressure Span Calibration.
Default = 1.0000
The upper PLog pressure limit, automatically scaled to the
pressure units selected at item 408. If PSI is the selected
pressure units, then item 419 will be the same as item 412.
Note; the value at item 419 may be manually edited to a
rounded-off number, if desired.
Default = 100.00
PLog gas pressure measured at the last wake-up. The pressure
value is scaled to the unit of pressure measurement selected at
item 408 and displayed with the appropriate number of
decimal positions as selected at item 420.