PAN – Setting e7w PAn ID (PAn)
1.
Enter SERVICE MODE,
2.
Use the UP/DOWN arrow buttons to select PAn and then press MODE.
3.
The current PAn value will be displayed on the screen.
4.
Use the UP/DOWN arrows to set the desired value ranging from 0 to 255.
5.
Press FAN, the unit beeps to confirm the value stored in the memory, display will be back to PAn.
Press the FC button to return SERVICE MODE or press UP arrow button to display next mode.
6.
Or
Press the FC button twice to exit SERVICE MODE
RF – Setting e7w RF Channel (rF)
1.
Enter SERVICE MODE,
2.
Use the UP/DOWN arrow buttons to select rF and then press MODE.
3.
The current rF channel value is displayed on the screen.
4.
Use the UP/DOWN arrows to set the desired value between 11 to 26.
5.
Press FAN, the unit beeps to confirm the value stored in the memory and display will be back showing rF.
Press the FC button to return SERVICE MODE or press UP arrow button to display next mode.
6.
Or
Press the FC button twice to exit SERVICE MODE
Appendix 3: Using the e7w Ping Feature
31 of 47
Honeywell Restricted
13 April 2020