You cannot change the e7w displayed target temperature, Fan Speed or HVAC Mode and a
warning triangle symbol is displayed
Possible Reasons:
The e7w has been placed into "Contractor" mode. When the e7w has been placed into Contractor mode , it
locks its target temperature to a defined value and locks out the e7w buttons.
be used during the hotel construction phase to set the room to a defined target temperature and prevent
tampering.
To exit the e7w out of Contractor mode:
1.
Enter SERVICE MODE
2.
Press UP/DOWN arrow buttons to select Ctr "- -"
3.
Press MODE button. This action displays "-" and Value.
4.
Press FAN button to turn off CONTRACTOR MODE. After turning off CONTRACTOR MODE e7w play beep
sound.
Press the FC button twice to exit SERVICE MODE
5.
The alert icon should clear