Appendix 2: Reading or Setting the Room ID, PAN ID and RF Channel into the e7w after it
has been Initialized
RID – Setting e7w Room ID (rld)
1.
Enter SERVICE MODE
2.
Use the UP/DOWN arrow buttons to select rld and then press MODE.
The current stored Room ID will scroll across the screen one numerical setting at a time, from highest to
lowest (left most to right most value). After the current value finishes scrolling, the 3 vertical Fan speed dots
displays indicating the high digit is displayed.
If the Room ID that scrolled was correct, press the FC button to return SERVICE MODE. Or, proceed with
the below steps the change the Room ID.
Note: The five-digit number is comprised of three fields: highest digit one, middle two digits, lowest two digits
(HI | MED | LO)
3.
Set HI (high) value, check fan speed dots, that indicates high value displayed (06 default value displayed).Use
UP/DOWN arrow button to change the value (range is 0-6). Press FAN to continue.
4.
Set MED (Medium) value, check fan speed dots, that indicates medium value displayed (55 default value
displayed). Use UP/DOWN arrow button to change the value (range is 0-99). Press FAN to Continue.
29 of 47
Honeywell Restricted
13 April 2020
Version 9.0
High Value