Setting The Pan Id During Initialization - Honeywell INNCOM e7w Troubleshooting Manual

Hide thumbs Also See for INNCOM e7w:
Table of Contents

Advertisement

4.
Set LO (Low) value, check fan speed dots, that indicates low value displayed (35 default value displayed). Use
UP/DOWN arrow button to change the value (range is 0-99).
5.
Press MODE button to store the new Room ID number scrolling across the display. The unit beeps to confirm
the value is stored in memory. Once the scrolling is completed, screen display rld.
Or
Press FAN button to move between three values to verify the Room ID.
Press UP arrow button to display PAn mode or press FC to return the INITIALLIZATION MODE.
6.

Setting the PAN ID during Initialization

1.
After PAn is displayed, press MODE . The default PAn value 0 is displayed.
2.
Use UP/DOWN arrow to change the value to the desired PAN ID(range is 0 to 255).
3.
Press FAN, the unit beeps to confirm the value stored in the memory and the display changes back to PAn.
27 of 47
Honeywell Restricted
13 April 2020
Version 9.0
Medium Value
Low Value