Fire Alarm Control Panel IQ8Control C / M
RS232 / TTY module (Part No. 784842)
Serial interface, alternatively RS232- or TTY
(20 mA) to connect external devices e.g. management
systems, Printers, Remote indicator panels etc.
Quiescent
current: approx. 35 mA @i RS232
approx. 55 mA @i TTY
3 Relay module (Part No. 787531)
Three bistable relay (monitoring possible) with
programmable operation mode normally open or normally
close.
Contact rating: max. 30 V DC / 1 A
Quiescent
current: approx. 5 mA
3 Relay common fault module (Part No. 787532)
Three bistable relay (monitoring possible) with
programmable operation mode normally open or normally
close and an additional common fault relay (energized in
normal mode).
Contact rating: max. 30 V DC / 1 A
Quiescent
current: approx. 15 mA
Observe permitted torque (max. 0.4 Nm) of the terminals!
94
not used
TxD (transmitt)
RxD (receive)
not used
not used
not used
Data GND (potential free)
not used
Tx - (transmitt)
not used
not used
Tx + (transmitt)
not used
Rx + (receive)
not used
Rx - (receive)
-
ext. device to relay K 1
+
+
ext. voltage e. g. +12 V
-
-
ext. device to relay K 2
+
-
ext. device to relay K 2
+
-
ext. device to relay K 1
+
+
ext. voltage for ext. device
to Relay K 1 e. g. +12 V
-
-
ext. device to relay K 2
+
ext. voltage for ext. device
+
to Relay K 2 e. g. +24 V
-
1 2
7 8
3 4 5
6
1 2
7 8
3 4 5
6
1 2
3 4 5
6
7 8
1 2
3 4 5
6
7 8
FB 798951.10.GB0 / 04.15