Honeywell ESSER IQ8Control C Installation Instruction page 63

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

6.4.4 Technical data Field device module
Operating voltage
Quiescent current
Fuse F1
Fuse F2, F3, F4
Relay K1
Relay K2, K3, K4
Fire department operating panel
Internal primary loop
Compatibility
The IQ8Control FACP's relays may only be connected to DC voltages. No AC voltage may be
applied, not even when a relay is programmed as a >non-monitored change-over contact<!
FB 798951.10.GB0 / 04.15
Fire Alarm Control Panel IQ8Control C / M
: Internal via the power supply module, +5 V DC / + 12V DC
: approx. 15 mA @ 12 V DC
:
T1A – slow blow (relay K1)
:
T2A - slow blow (relays K2 to K4)
Relay for connecting a master box. May also be used as a freely
:
programmable relay.
Selection of operating mode and emergency function by means of
jumpers.
Contact rating when used as a >non-monitored change-over
contact< contact rating < 30 V DC/ max.1 A.
No dry contact cause of the integrated EMI protection.
Relay with common function. May also be used as a freely
:
programmable relay.
Selection of operating mode and emergency function by means of
jumpers.
Contact rating when used as a >non-monitored change-over
contact<, contact rating < 30 V DC/ max.2A
No dry contact cause of the integrated EMI protection.
: 8 digital inputs
8 outputs - max. 12 V DC / 20 mA per output
: monitored 10 k  (normal) / 5 k  (FIRE) / 1 k  (fault)
Application e.g. for essernet
: Part No.772479  Field device module without micro module slot
Part No.772477  Field device module with micro module slot
®
-emergency operation
63