Honeywell ESSER IQ8Control C Installation Instruction page 136

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C / M
Wiring FACP IQ8Control
M
Fig. 121: Wiring Printer with paper take-up reel
Observe permitted torque (max. 0.4 Nm) of the terminals!
Customer data programming with tools 8000
The printer must be programmed with the tools 8000 programming software from V1.15 or higher as a
>Printer with take up reel for Serial 2< in the panel configuration.
Fig. 122: Selecting the printer
136
4
X23 Printer
+UBext T2A
+ -
GND
switched +12 V ext.
Ribbon cable
Basic module
IQ8 Control
+UBext.
F4
BR7
Printer
GND
FB 798951.10.GB0 / 04.15