Honeywell ESSER IQ8Control C Installation Instruction page 119

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

Trouble
Possible Cause
Code No.
There are more detectors on the
069
loop than programmed in the
customer data.
Error during detector data
070
allocation.
This detector change may only
be performed with the service PC
080
because this detector required
customer data that cannot be
generated in the FACP itself.
The detector has been replaced
with an OTI-detector. The sensor
081
type has changed in comparison
with the customer data.
The detector has been replaced
with an OT-detector. The sensor
082
type has changed in comparison
with the customer data.
The detector has been replaced
with an I-detector. The sensor
083
type has changed in comparison
with the customer data
The detector has been replaced
with a TM-detector. The detector
084
type has changed in comparison
with the customer data.
The detector has been replaced
with a TME-detector. The
085
detector type has changed in
comparison with the customer
data.
The detector has been replaced
with a TD-detector. The detector
086
type has changed in comparison
with the customer data.
The detector has been replaced
with an O-detector. The detector
087
type has changed in comparison
with the customer data.
Detector circuitry has been
changed at detector location.
088
Now detector has neither external
circuit (relay / LED) nor isolating
relay.
FB 798951.10.GB0 / 04.15
Fire Alarm Control Panel IQ8Control C / M
1st. measure
If this change is not desired,
connect service PC and run
a wiring recognition. Re-
program customer data.
Perform detector data
assignment again.
If this change is not desired,
connect service PC and run
a wiring recognition. Re-
program customer data.
Check whether detector type
change is desired; if it is,
activate loop.
Check whether detector type
change is desired; if it is,
activate loop.
Check whether detector type
change is desired; if it is,
activate loop
Check whether detector type
change is desired; if it is,
activate loop.
Check whether detector type
change is desired; if it is,
activate loop.
Check whether detector type
change is desired; if it is,
activate loop.
Check whether detector type
change is desired; if it is,
activate loop.
If this change is desired,
connect service PC and run
a wiring recognition.
Re-program customer data.
2nd. measure
If this change is not desired,
connect service PC and run a
wiring recognition. Re-program
customer data.
---
---
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
---