Fire Alarm Control Panel IQ8Control C / M
®
7.1.1 esserbus
loop module (Part No. 784382 / 784382.10 / 784382.D0)
The loop module allows for esserbus
from V1.15.
®
Fig. 57: Exampleesserbus
Loop module
K2 (B)
K1 (A)
Fig. 58: Loop module (Part No. 784382 / 784382.10 / 784382.D0)
Connect cable shielding of the loop only at one side.
When using the module in door control systems, place the enclosed labels on or in the FACP
housing (see chapter 14.1).
X 1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1, K2
Bi-directional loop interrogation by loop isolators
(K1 = A+, A- / K2 = B+, B-)
LED 1
(SMD) red, flashing
(SMD) red, lit
(SMD) yellow, lit
LED 2
(SMD) red, flashing
LED 3
(SMD) red, lit
LED 4
(SMD) yellow, flashing
(SMD) yellow, flashing rapidly
68
®
connection and is configured with Programming software tools 8000
esserbus
®
LED 1
in normal mode in time with communication on the loop
Short circuit on loop
Module faulty
+ 24 V power supply failure or communication to
control panel processor interrupted
Module in CPU failure mode
(control panel CPU failure)
Processor program running – normal mode
Module in test mode
Fire alarm and extinguishing
computer 8010
X1
LED 2
LED 3
LED 4
FB 798951.10.GB0 / 04.15