Fire Alarm Control Panel IQ8Control C / M
Trouble
Possible cause
text
An error has been detected
when an loop was switched
start-up
on; normal operation is
impossible.
When an loop was switched
on, more detectors were found
than programmed in the
customer data or more
Detector >
detectors were found in an
EDD detector zone than
programmed in the customer
data.
When an loop was switched
on, fewer detectors were
Detector <
found than programmed in the
customer data.
The wiring configuration of this
Topolog.
loop cannot be precisely
determined.
A detector has been found in
the corresponding loop which
Serial No
is not programmed in the
customer data.
The 1st ring is inoperable in a
redundant essernet
Line A
The 2nd ring is in operation.
The 1st ring is inoperable in
Line B
redundant essernet
Fault of the A/D converter
card on the Basic module or
AD conv.
the A/D converter of the loop
module is defective.
122
1st. measure
Localise the source with
programming software tools
8000 switch on or reconfigure
the loop.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop For EDD detector
zones, check the number of
detectors and reprogram the
customer data if necessary.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop.
Localise the source with
programming software tools
8000, switch on or reconfigure
the loop.
Have detectors been
exchanged and is the error
plausible?
®
wiring.
Check essernet
Check essernet
®
wiring.
Replace Basic module or
micro module.
If yes, execute the Exchange
detector function for this loop
to update data.
Check the essernet
®
wiring
switchover module and
replace if necessary.
Check switch over module
®
wiring
and replace if necessary.
2nd. measure
---
---
---
---
®
---