Chapter 6 - Testing ControlNet Trunk Cables
6.3.1

To test each length of cable

1. With no cable connected, verify that your TDR screen appears as shown.
Settings are:
l
l
2. Connect one end of your cable to the cable jack on the TDR; do NOT terminate the loose end. You
screen should appear as shown in one of the following figures.
If your settings are:
l
l
l
l
Do NOT connect together and attempt to test multiple lengths of ControlNet trunk cable.
l
Doing so will invalidate the test and will not ensure accurate results.
Both ends of every ControlNet trunk cable section must be tested.
l
Keep the TDR batteries (if used) fully charged.
l
The cables connectors must be installed using the correct tools. If it appears the
l
connection was made with pliers, channel-locks, or vice-grips, reject the cable.
Look for folds or kinks in the cable sheathing, indicating that the minimum bend-radius
l
was exceeded; reject the cable.
Do not compromise on the accuracy of the test terminator. This test procedure depends
l
on the delta difference between the terminator and the cable section under test.
X10 & .5ft/Div
0 dB & 0 dB Loss
2 m (6.5 ft) example
X10 & .5ft/Div
0 dB & 0 dB Loss
No Terminator
- 44 -