HONEYWELL EXCEL 5000 OPEN SYSTEM
CONTENTS
Safety Information ............................................................. 4
General Safety Information ............................................ 4
System Overview............................................................... 5
System Architecture....................................................... 5
I/O Modules ................................................................... 6
Interfaces and Bus Connections .................................... 9
Technical Data............................................................... 9
System Data............................................................. 9
Standards................................................................. 9
Operational Environment.......................................... 9
Planning ........................................................................... 10
Overview...................................................................... 10
Transformer Selection.................................................. 10
Power Consumption............................................... 10
Connectable Power Supplies ................................. 10
Power Supply of Field Devices............................... 11
Fusing Specifications ................................................... 11
System Protective Earth Grounding............................. 11
Lightning Protection ..................................................... 11
Panel Bus Topologies .................................................. 11
Bus Topologies.......................................... 12
C-Bus Topologies ........................................................ 12
Accessories ................................................................. 12
Preconfigured Connection Cables.......................... 12
Bus Termination Modules .................... 13
Cable Specifications .................................................... 13
Power Supply Cables ............................................. 13
Panel Bus Cables................................................... 13
Bus Cables .......................................... 14
Field Device Cables ............................................... 14
C-Bus Cables ......................................................... 15
Dimensions .................................................................. 16
Controller Module................................................... 16
I/O Modules............................................................ 16
Mounting/Dismounting Modules .................................... 17
Mounting Sockets................................................... 17
Connecting Sockets ............................................... 18
Dismounting Sockets ............................................. 19
Mounting Electronic Modules ................................. 19
Dismounting Electronic Modules ............................ 20
Copyright © 2008 Honeywell GmbH ! All Rights Reserved
Excel 800 LION
INSTALLATION AND COMMISSIONING INSTRUCTIONS
Operating the Individual Switches .......................... 21
Mounting Swivel Label Holders .............................. 22
Dismounting Swivel Label Holders ......................... 22
Wiring and Setting Up the System ................................. 23
General Safety Considerations .................................... 23
Wiring Push-in Terminals............................................. 23
Connecting Power Supply............................................ 24
Single or the First Transformer............................... 24
Additional Transformer ........................................... 24
Single Cabinet........................................................ 25
Connecting Panel Bus and L
Controller Systems....................................................... 26
I/O Modules with Each Other ................................. 26
I/O Modules to the Controller ................................. 26
Setting I/O Bus Switch ................................................. 28
Connecting Field Devices ............................................ 29
Cabling Field Devices............................................. 29
Commissioning I/O Modules ........................................ 30
Updating Software ....................................................... 30
Software with Panel Bus I/O Modules .................... 30
Bus Termination................................... 31
Connecting via C-Bus .................................................. 32
Connecting to the Controller................................... 32
How to Shield ......................................................... 32
Connecting HMIs or Laptops ....................................... 32
3.4
SYSTEM
Bus Mixed
Bus I/O Modules ......... 30
Bus I/O Modules ............ 30
Bus.................................... 31
EN1B-0375GE51 R0308

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Excel 800 LION

  • Page 1: Table Of Contents

    Mounting/Dismounting Electronic Modules ....19 Setting the C-Bus Termination Switch....32 Mounting Electronic Modules ......... 19 How to Shield ............32 Dismounting Electronic Modules ......20 Connecting HMIs or Laptops ........32 Copyright © 2008 Honeywell GmbH ! All Rights Reserved EN1B-0375GE51 R0308...
  • Page 2 Appendix 1: System Protective Earth Grounding ..76 Technical Data ............51 Excel 800 LION Systems and SELV......76 Status LEDs ............51 Excel 800 LION Systems and Standard EN60204-1 ..76 Configuration as Fast Totalizer .......51 General Information about EN60204-1 ....76 Connection Example..........52 When is EN60204-1 Applicable to Excel 800 LION Relay Output Modules ..........53...
  • Page 3 Excel 800 LION Troubleshooting ............80 Appendix 3: Sensor Characteristics ......81 BALCO 500..............81 NTC 20 kΩ..............82 PT 1000 ............... 83 NI1000TK5000............. 85 NTC 10 k ..............86 PT 3000 ............... 87 Trademark Information Echelon, LON, L , Neuron, are...
  • Page 4: Safety Information

    Rules regarding electrostatic discharge should be ► suitable for use in residential followed. controls, commercial controls, If the Excel 800 LION System is modified in any way, ► in a clean environment. except by the manufacturer, all warranties concerning Overvoltage Category II operation and safety are invalidated.
  • Page 5: System Overview

    Excel 800 LION System Overview System Architecture An Excel 800 LION System consists of the CLLIONLC01 Controller and various I/O modules. The CLLIONLC01 Controller provides interface connections, which allow connection to external systems. Auxiliary parts enable special features. Fig. 1 Excel 800 LION System architecture Fig.
  • Page 6: I/O Modules

    Dark-gray Bus I/O modules ORKS Terminal Sockets Table 2 Color coding of Excel 800 LION Modules I/O modules are mounted on the appropriate terminal sockets. Panel Bus I/O modules and L Bus I/O ORKS modules use the same terminal sockets.
  • Page 7 Excel 800 LION I/O Module Overview Panel Bus ORKS Description Inputs Outputs Manual controls LEDs module Bus module CLIOP821A CLIOL821A Analog input module – – – CLIOP822A CLIOL822A Analog output module – – 8 status LEDs CLIOPR822 CLIOLR822A Analog output module –...
  • Page 8 …824 disconnection of individual XS812RO I/O signals …825 For 24 V applications only 2 rows of 7 terminals Auxiliary terminal All Excel 800 LION I/O XS814 connected to each other for package modules redistributing voltage Connects 3 relay commons, …824...
  • Page 9: Interfaces And Bus Connections

    Excel 800 LION Standards Interfaces and Bus Connections The Excel 800 LION System can be connected to the Protection class IP20 following devices and systems: Product standard EMC EN 60730-2-9:2005-10 Panel Bus Testing electrical IEC68 • For communication with up to 16 Panel Bus I/O modules components •...
  • Page 10: Planning

    130 mA …824 140 mA 90 mA …825 140 mA 90 mA Table 10 Power consumption of Excel 800 LION System components depending on power supply Connectable Power Supplies Honeywell CRT Series (Europe) Transformer Primary side Secondary side CRT 2...
  • Page 11: Power Supply Of Field Devices

    Low Voltage). Earth grounding is therefore not Standard Transformers (Europe, North America) recommended. Standard commercially available transformers used to However, if compliance with EN60204-1 is required, see supply power to Excel 800 LION Systems must fulfill the Appendix 1. following specifications: Output voltage Impedance...
  • Page 12: Lon Works Bus Topologies

    RJ45 plug with clip at front SHIELD XI582 Star connection is not allowed because uncontrollable line reflections may occur. Instead of an Excel 800 LION Controllers, other C-Bus controllers (e.g., the Excel 500, Excel 100, Excel 50) can also be connected. XW882 Fig. 5...
  • Page 13: Lon Works Bus Termination Modules

    Excel 800 LION XW885 Cable Details Bus Termination Modules ORKS RS232 plug RJ45 plug with clip at front sub-D male of laptop SHIELD Type Description 209541 Bus termination module ORKS XAL-Term connection and ORKS termination module, which can be mounted on DIN rails and in fuse...
  • Page 14: Lon Works Bus Cables

    Echelon in their FTT-10A User Guide. ≤ ≤ ≤ ≤ 400 m (1300 ft) ≤ ≤ ≤ ≤ 100 m (300 ft) • The cable recommended by Honeywell is the level IV, Type of signal (Fig. 40 on p. 29) (Fig.
  • Page 15: C-Bus Cables

    Excel 800 LION C-Bus Cables Note Observe national regulations for C-Bus cables! • For Europe, only shielded cable is permitted. • For the U.S., shielded or unshielded cable can be used. Cable type Description Recommended for J-Y-(ST)Y shielded, Europe, inside cabinet 2 x 2 x 0.8...
  • Page 16: Dimensions

    Excel 800 LION Dimensions Controller Module 144 -/+ 0.3 92.75 -/+ 0.3 Fig. 11 Controller module, outside dimensions (in mm) I/O Modules Wiring channel 89.5 -/+ 0.3 94.1 -/+ 0.3 LOCK XS814 Auxiliary Terminal Sockets Wiring 30.6 (optional) channel Fig. 12...
  • Page 17: Mounting/Dismounting Modules

    • When using both Panel Bus and L Bus I/O ORKS energize the system. modules in an Excel 800 LION System, group both Do not reconnect the power supply until you have ► Panel Bus modules (light gray) and L...
  • Page 18: Connecting Sockets

    I/O modules separately. When using both Panel Bus and L ► ORKS I/O modules in an Excel 800 LION System, L ORKS Bus I/O modules must be connected to the controller via LON terminals 11 … 14. Position the bridge connector on terminals 71 … 74 of the right hand terminal socket or controller and on terminals 75 …...
  • Page 19: Dismounting Sockets

    Excel 800 LION Mounting/Dismounting Electronic Modules Dismounting Sockets Disconnecting Sockets Mounting Electronic Modules Release all bridge connectors before removing the controller module and/or the terminal sockets from the DIN rail. Note Press down at the same time both the gray side wings ►...
  • Page 20: Dismounting Electronic Modules

    Excel 800 LION Mounting/Dismounting Manual Disconnect Dismounting Electronic Modules Modules Note XS812 and XS812RO Manual Disconnect Modules are Electronic modules can be removed from the socket or mounted on the terminal socket appropriate for the inserted into the sockets without switching off the power electronic module, see Table 4 on page 7.
  • Page 21: Operating The Individual Switches

    Excel 800 LION Mounting/Dismounting Auxiliary Terminal Operating the Individual Switches Packages Use a screwdriver to open/close the appropriate ► disconnector switches of the manual disconnect modules. Mounting Auxiliary Terminal Packages Push the auxiliary terminal package onto the grooves of ►...
  • Page 22: Mounting/Dismounting Cross Connectors

    Excel 800 LION Mounting/Dismounting Cross Connectors Mounting/Dismounting Swivel Label Holders Note The long cross connector (incl. in the scope of the delivery) Note can be mounted to the XS824-25, as required (see Fig. 28). A swivel label holder is included in the scope of delivery of It can be dismounted (see Fig.
  • Page 23: Wiring And Setting Up The System

    General Safety Considerations Wiring Push-in Terminals • When connecting the CLLIONLC01 Controller Module or The Excel 800 LION System is equipped with push-in terminals for easy wiring. Excel 800 LION I/O modules, both VDE, National Electric Code (NEC) or equivalent, and any local regulations...
  • Page 24: Connecting Power Supply

    Additional Transformer Connect the additional transformer in a second room or ► The Excel 800 LION System can be powered by one or cabinet to terminals 73 and 74 or 77 and 78 of an more external transformers. I/O module.
  • Page 25: Connecting Single Bus Controller Systems

    Excel 800 LION Connecting Single Bus Controller Systems Panel Bus I/O Modules in Separate Rooms In this scenario, communication and reference voltage This section describes how to connect a controller system (24 V0) must be connected between the rooms. which uses Panel Bus I/O modules only or L...
  • Page 26: Lonworks Bus I/O Modules In Separate Rooms

    Excel 800 LION Connecting Panel Bus and L LonWorks Bus I/O Modules in Separate Rooms ORKS Mixed Controller Systems In this scenario, only communication lines must be connected between the rooms. Connect the last module of room 1 to the first module of ►...
  • Page 27 Excel 800 LION Panel Bus I/O modules Panel Bus I/O modules CLLIONLC01 XF... LonWorks Bus I/O modules Fig. 35 Mixed bus system – correct wiring Panel Bus I/O modules LonWorks Bus modules CLLIONLC01 Fig. 36 Mixed bus system – incorrect wiring...
  • Page 28: Setting Address Of Panel Bus I/O Modules

    Excel 800 LION Setting Address of Panel Bus I/O Modules Setting I/O Bus Switch During CARE engineering, each Panel Bus I/O module is Set the I/O Bus switch S2 of the CLLIONLC01 Controller ► assigned its own unique address. For the sake of clarity for...
  • Page 29: Connecting Field Devices

    Excel 800 LION Connecting Field Devices Cabling Field Devices Connecting Field Devices with Power Supply Cable Routing Depending on the distance from the controller, field devices Route low-voltage signal and output cables separately from can be supplied by the controller or need a separate mains cables.
  • Page 30: Commissioning I/O Modules

    Excel 800 LION Commissioning I/O Modules Commissioning Panel Bus I/O Modules During CARE engineering, the HEX address of the Panel I/O modules is defined. Note With Panel Bus I/O modules it is essential that the HEX switch be set to the address assigned by CARE.
  • Page 31: Connecting To External Systems Or Interfaces

    Observe the rules regarding electrostatic discharge. ► doubly-terminated FTT network Connecting via L ORKS Via a L Bus, an Excel 800 LION System can be ORKS connected to other controller systems, to additional Bus I/O modules, or to laptops and HMIs. ORKS Fig. 42...
  • Page 32: Connecting Via C-Bus

    Connecting Modems Switch Baud rate setting S1 An Excel 800 LION System can be connected to a modem 9.6k all Up to 9600 baud (default setting) or an ISDN terminal adapter via the Modem Interface of the CLLIONLC01 Controller Module by means of the XW786...
  • Page 33: Description Of The Cllionlc01 Controller Module

    Excel 800 LION Description of the CLLIONLC01 Controller Module Overview Fig. 45 Connections to the CLLIONLC01 Controller Legend Power supply for I/O modules I/O Bus communication terminals interface ORKS service button ORKS service LED ORKS C-Bus Tx LED C-Bus Rx LED...
  • Page 34: Cllionlc01 Terminals

    Excel 800 LION Features CLLIONLC01 Terminals Interface and Terminals ORKS The CLLIONLC01 Controller Module features • An RJ45 socket serving as an interface to connect laptops or HMIs to the L ORKS 8 7 6 5 4 3 2 1 •...
  • Page 35: C-Bus Tx Led And Rx Led

    Excel 800 LION program changes) to FLASH memory. C-Bus Tx LED and Rx LED The CLLIONLC01 Controller Module is equipped with a Tx LED (status: yellow/OFF) and an Rx LED (status: yellow/OFF). C-Bus Fig. 50 C-Bus Tx LED (1) and Rx LED (2)
  • Page 36: Hmi Interface

    Excel 800 LION HMI Interface Alarm and Power LEDs The controller module is equipped with an HMI Interface for The CLLIONLC01 Controller Module is equipped with an the connection of HMIs, e.g., XI582 Operator Interface or a alarm LED and a power LED.
  • Page 37: Watchdog

    Excel 800 LION Power LED (2, green) Modem Interface Normal operation The controller module is equipped with a modem interface Flashing One or more of the internal voltage for the connection of a modem or an ISDN terminal adapter. supplies are outside of the permissible ranges.
  • Page 38: I/O Bus Switch S2

    Excel 800 LION I/O Bus Switch S2 C-Bus Termination Switch S1 The CLLIONLC01 Controller Module features a 2-position The CLLIONLC01 Controller Module features a 3-position I/O Bus switch S2. C-Bus termination switch S1. I/O Bus switch S2 must be set in accordance with the kind...
  • Page 39 Excel 800 LION EN1B-0375GE51 R0308...
  • Page 40: Description Of The I/O Modules

    XS821-822 Terminal socket Light gray • Module addressing for Panel Bus Hex switch I/O modules Table 41 Excel 800 LION Analog Input Modules LEDs located on the I/O Module Features Feature Function • 8 analog inputs • Service information, see section Service LED •...
  • Page 41: Terminals

    Excel 800 LION Terminals Technical Data • 0(2) ... 10 VDC Input • 0(4) ... 20 mA (via external 499 /0.25 % resistor • NTC20k (-50…+150 ° C; default) • PT1000-1 (-50…+150 ° C) • PT1000-2 (0…+400 ° C) • PT3000 (-50…+150 ° C) •...
  • Page 42: Internal Impedance When Connecting Sensors

    Excel 800 LION Internal Impedance when Connecting Sensors Fig. 59 Analog input low impedance (input circuit for PT1000, Balco500, PT3000, NI1000TK5000, slow binary input) Fig. 60 Analog input high impedance (input circuit for voltage input for active sensors) Fig. 61...
  • Page 43: Connection Examples

    Excel 800 LION Connection Examples Active Sensor and Potentiometer CLIOP821A Analog Input Module V~ 0 AI2 AI3 AI4 AI5 AI6 AI7 AI8 CLIOP821A Shield internally connected to DIN rail 25 26 Optional Aux. Terminal Module XS814 A1 A2 A3 A4 A5 A6 A7 1 2 3 4 5 6 7 Aux.
  • Page 44 Excel 800 LION Passive Sensor and 0 (4) … 20 mA Signal CLIOP821A Analog Input Module V~ 0 V~ 0 AI2 AI3 AI4 AI5 AI6 AI7 AI8 CLIOP821A CLIOP821A 25 26 External 499 Ω resistor with twin wire-end ferrules required Temp.
  • Page 45: Analog Output Modules

    XS821-22 Terminal socket Light gray Table 45 Excel 800 LION analog output modules Features • 8 analog outputs; can also be configured per output as binary outputs (0 … 10 V, 2 … 10 V, ON/OFF, or floating) Fig.
  • Page 46: Technical Data

    Excel 800 LION Technical Data Modules with Manual Overrides The CLIOPR822A/CLIOLR822A Analog Output Modules are equipped with manual overrides: one rotary knob for each Voltage rating 0(2)…11 V (default) analog output. Current rating max. ±1 mA The manual overrides can be set manually to either "auto"...
  • Page 47: Connection Example

    Excel 800 LION Connection Example CLIOP822A Analog Output Module V~ 0 NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8 CLIOP822A Shield internally connected to DIN rail 25 26 Optional Aux. Terminal Module XS814 XS814 A1 A2 A3 A4 A5 A6 A7...
  • Page 48: Synchronization Behavior Of Analog Output Module Configured As Floating Output

    Excel 800 LION This updating (synchronization) is performed: Synchronization Behavior of Analog Output • If the calculated position of the actuator Module Configured as Floating Output < lower synchronization threshold (2 %) In order to regularly update the real actuator position with = synchronization towards 0 % •...
  • Page 49 Excel 800 LION CLIOP822A Analog Output Module CLIOP822A NC NC AO1 AO2 AO3 AO4 AO5 AO6 AO7 AO8 21 22 2 3 4 5 6 7 8 Shield internally Connected to DIN RAIL GND GND GND GND GND GND GND GND...
  • Page 50: Binary Input Modules

    BI11 BI12 XS823 Terminal socket Light gray Table 49 Excel 800 LION Binary Input Modules GND GND GND GND GND GND GND GND GND GND GND 25 26 Features • 12 binary inputs • 12 configurable status LEDs (green/red, yellow/OFF) Fig.
  • Page 51: Technical Data

    Excel 800 LION Technical Data Configuration as Fast Totalizer Using CARE, the binary inputs can be configured as fast totalizers for operation in conjunction with devices equipped Input type Dry-contact or open collector with an open collector output. Current rating (closed...
  • Page 52: Connection Example

    Excel 800 LION Connection Example CLIOP823A Binary Input Module CLIOP823A BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 2 3 4 5 6 7 8 9 10 11 12 Shield internally connected to DIN rail 13 14 15 16 17...
  • Page 53: Relay Output Modules

    Table 5 on page 8. connector (incl. in scope of the delivery) NOTICE Table 52 Excel 800 LION Relay Output Modules Risk of malfunction! Features Cross connectors may only be used if the same voltage is used on all relays they connect.
  • Page 54: Terminals

    Excel 800 LION Terminals Permissible Loads Max. load Min. load Per relay 19…250 VAC – output current at cos φ ≥ 0.6: 12 A module (total) 1…29 VDC 12 A resistive, 3 A inductive Relay block 1 Relay block 2 Per normally 19…250 VAC...
  • Page 55: Connection Example

    Excel 800 LION Connection Example CLIOP824A Relay Output Module Cross Connector (Factory mounted) Shield internally connected to DIN RAIL Optional Aux. Terminal Module XS514 A1 A2 A3 A4 A5 A6 A7 1 2 3 4 5 6 7 Field Device...
  • Page 56 Excel 800 LION Fig. 77 CLIOP824A connection example (relay blocks with low and line voltage) For fusing specifications see section "Fusing Specifications" on page 11. EN1B-0375GE51 R0308...
  • Page 57: Floating Output Module

    Excel 800 LION Floating Output Module WARNING Features Risk of electric shock or equipment damage! • Type: CLIOPR825A Floating Output Module Low voltage and line voltage must not be wired within the same relay block. • Housing: light gray Wire low voltage e.g., to relay block 1 and line voltage to ►...
  • Page 58: Terminals

    Excel 800 LION Terminals Manual Overrides The floating output module is equipped with manual overrides: one rotary knob for each floating output. These manual overrides can manually be set to either "Auto" or "0 … 100 %" (infinitely adjustable). Actuator 1...
  • Page 59: Connection Example

    Excel 800 LION Connection Example CLIOPR825A Floating Output Module Cross connector (factory -mounted) Shield internally connected to DIN rail Optional aux. Terminal Module XS814 A1 A2 A3 A4 A5 A6 A7 1 2 3 4 5 6 7 Floating actuator...
  • Page 60: Description Of Extra Parts

    Excel 800 LION Description of Extra Parts Manual Disconnect Modules Types Manual disconnect Corresponding I/O modules module CLIO… XS812 …821 …822 …823 XS812RO …824 …825 Table 59 Manual disconnect modules For mounting the manual disconnect modules, see Fig. 23 on page 20.
  • Page 61: Xs814 Auxiliary Terminal Package

    Excel 800 LION XS814 Auxiliary Terminal Package Cross Connectors Features XS815 Cross Connector Features • Type: XS814 Auxiliary Terminal Package • For connecting the common terminals of all 6 relays. This is permitted when all terminal blocks carry the same •...
  • Page 62: Lon Software Interface Description

    CLIOL821A Analog Input Module For the CLIOL821A Analog Input Module the L LonTalk Protocol Profile 520 "Analog Input" has been assigned per input. Excel 800 LION L Bus I/O Modules use a L ORKS Each input object has its own configuration properties,...
  • Page 63: Analog Sensor Output - Nvoaivaluepct[ ]

    Excel 800 LION Temperature Sensor Output – nvoAiTempP[ ] Default Service Type This network variable output represents the temperature for The default service type of these variables is the appropriate input, if configured for temperature sensor, unacknowledged. except PT1000-2. Range: see Table 43 and Table 44 on page 41.
  • Page 64: Cliol(R)822 Analog Output Module

    Excel 800 LION CLIOL(R)822A Analog Output Module Analog Output Control Level – nviAoValuePct[ ] This network variable is used to drive the analog output to For the CLIOL822A/CLIOLR822A Analog Output Module 0 … 100 %. the L open-loop actuator object has been assigned If both nviAoSwitch[ ] and nviAoValuePct[ ] receive valid per output.
  • Page 65: Analog Output Feedback - Nvoaoposnfb[ ]

    Excel 800 LION Analog Output Feedback – nvoAoPosnFb[ ] Analog Output Command – nviAoSwitch[ ] This value represents the current status of the analog output This network variable is used to drive the analog output to including feedback related to manual override initiated from 0 …...
  • Page 66: Cliol823A Binary Input Module

    Excel 800 LION CLIOL823A Binary Input Module Fast Binary Input – nvoDiSwitch[ ] This network variable output represents the logical state of a One instance of the L open-loop sensor object has fast binary input connected to the binary input terminals.
  • Page 67: Cliol(R)824 Relay Output Module

    Excel 800 LION CLIOL(R)824A Relay Output Module Relay Output Command – nviDoSwitch[ ] This network variable is used to drive the relay output. One instance of the L open-loop sensor object has It is typically bound to a L control device issuing an...
  • Page 68: Troubleshooting

    Excel 800 LION Troubleshooting Testing Wiring Connections The push-in terminals feature small holes (1 mm in diameter) which can be used to measure the signals. Insert a probe (1) as shown on the right. ► Fig. 96 Testing wiring connections...
  • Page 69: Alarm Led (Red)

    Excel 800 LION Alarm LED (red) Case Alarm LED Meaning Remedy Normal operation No action necessary Watchdog alarm output is powered Try powering down and then ► – The controller has encountered a powering up the CLLIONLC01. hardware problem If problem persists, check and – if ►...
  • Page 70: Lon Works Service Led

    Excel 800 LION Service LED ORKS Fig. 97 Flashing pattern of the L service LED ORKS The L service LED of the controller module displays the following flashing patterns indicating possible failure modes: ORKS case When can it occur? Meaning...
  • Page 71: C-Bus Tx And Rx Leds

    Excel 800 LION C-Bus Tx and Rx LEDs case C-Bus LEDs Meaning Remedy If the C-bus is functioning properly, then the Both LEDs are flashing No action necessary CLLIONLC01 Controller is functioning properly If the C-bus is not functioning properly, then Check C-bus termination switch S1 ►...
  • Page 72: I/O Modules Troubleshooting

    Excel 800 LION I/O Modules Troubleshooting Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the ► inputs/outputs of the …821, …822, …823 I/O modules.
  • Page 73: Service Led Of I/O Modules

    Excel 800 LION Service LED of I/O Modules case Service LED Meaning Remedy ► Replace hardware If the power LED is also OFF, then LED remains OFF after power-up – Defective device hardware – Possible power supply problems, clock problems, defective processor •...
  • Page 74: Led Test For I/O Modules

    Excel 800 LION LED Test for I/O Modules Press the service button S1 of the I/O module, e.g. using a paperclip. ► – The service LED and all other LEDs of that Panel Bus I/O module light up for as long as the service button is pressed.
  • Page 75: Analog Output Modules Troubleshooting

    Internal undervoltage detection has been Replace hardware ► activated Table 81 Failure modes of floating output modules A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under: http://web.ge51.honeywell.de/tac EN1B-0375GE51 R0308...
  • Page 76: Appendix 1: System Protective Earth Grounding

    Furthermore, SELV offers the greatest possible safety For connection details, refer to the following examples. ► against electrical impact. To support SELV, all Honeywell external (CRT series) or Example 1 internal transformers comply with standard EN60742. Connecting a single transformer with multiple Excel 800 Earth grounding is therefore not recommended.
  • Page 77 Excel 800 LION Example 2 Example 3 Connecting an Excel 800 LION System together with other Connecting a C-Bus with controllers earth-grounded as per controllers earth-grounded as per EN60204-1 EN60204-1 Notes Notes • Use a noise-free earth ground inside the cabinet.
  • Page 78: Appendix 2: Remote Communications

    Excel 800 LION Appendix 2: Remote Communications Modem or ISDN Terminal Adapter For remote communications with up to three centrals, a modem or ISDN terminal adapter can be connected directly Connection to the modem interface of the CLLIONLC01 Controller Module.
  • Page 79: Modem Set-Up

    Excel 800 LION the modem not to wait for the public phone system dial tone, Modem Set-up and writes this to nonvolatile memory. Set-up for Special Modem Behavior Standard Modem Behavior If special modem/ISDN terminal adapter behavior is If no special modem behavior is required, there is no need required, the communication device should be set up to set up or initialize the modem/ISDN terminal adapter.
  • Page 80: Westermo Td-33 Setup Parameters

    ISDN terminal adapter must be consulted. A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under: http://web.ge51.honeywell.de/tac Go there, and enter the catchword "modemfaq" in the ►...
  • Page 81: Appendix 3: Sensor Characteristics

    Excel 800 LION Appendix 3: Sensor Characteristics Note The following sensor characteristics do not include failures due to: • Sensor failures • Wiring resistance or wiring failures • Missreadings due to a meter connected to measure resistance or voltage at the input BALCO 500 Temp.
  • Page 82: Ntc 20 Kω

    Excel 800 LION NTC 20 kΩ Ω Ω Ω Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] [° C] voltage [V] [° C] voltage [V] [°...
  • Page 83 Excel 800 LION PT 1000 Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] [° C] [Ω] voltage [V] [° C] [Ω] voltage [V] [° C] [Ω]...
  • Page 84 Excel 800 LION Resistance Resistance Resistance Resistance Temp. Terminal Temp. Terminal Temp. Terminal Temp. Terminal Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] [° C] [Ω] voltage [V] [° C] [Ω] voltage [V] [° C] [Ω] voltage [V] [°...
  • Page 85: Ni1000Tk5000

    Excel 800 LION NI1000TK5000 Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal [° C] [k ] voltage [V] [° C] [k ] voltage [V] [° C] [k ] voltage [V] [° C] [k ] voltage [V] 1081.4...
  • Page 86: Ntc 10 K

    Excel 800 LION NTC 10 k Resistance Resistance Resistance Resistance Temp. Terminal Temp. Terminal Temp. Terminal Temp. Terminal Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] [° C] [kΩ] voltage [V] [° C] [kΩ] voltage [V] [°...
  • Page 87 Excel 800 LION PT 3000 Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] Ω] [° C] [kΩ] voltage [V] [° C] [kΩ] voltage [V] [° C] [kΩ]...
  • Page 88 Excel 800 LION Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D-71101 Schönaich...