General Settings 2 - Honeywell NOTIFIER UDACT-2 Instruction Manual

Universal digital alarm communicator
Table of Contents

Advertisement

Programming
- 32 addresses - 1-32 - for point reporting
!
- The NFS2-640, NFS-640, NFS-320/NFS-320SYS use:
- two monitoring addresses - 20 and 21 - for zone reporting.
- ten monitoring addresses - 22 through 31 - for point reporting.
- The AFP-300 and AFP-400 use:
- two monitoring addresses - 11 and 12 - for zone reporting
- seven addresses - 13 through 19 - for point reporting.
- The AFP-200 uses two monitoring addresses - 1 and 2 - for zone reporting.
Start Daylight Savings Time - Enter start day, month, time.
End Daylight Savings Time - Enter end day, month, time.
UDACTM: This box activates for NFS2-640 and NFS-320 panels when a point reporting type is selected. Check the box to enable 4-
point UDACT-2 reporting (Alarm, Trouble, Dirty 1, Dirty 2) when the UDACT-2 is programmed as Option 2 in ACS programming on
these panels.
Note: This option enables the UDACT-2 to report Alarm, Trouble, Dirty 1 (Maintenance) and Dirty 2 (Maintenance Urgent) per address-
able detector. Note that enabling this option will limit the system to only report the first 100 detector (L1D1 - L1D100/L2D1-L2D100)
and module (L1M1-L1M100/L2M1-L2M100) addresses per loop. Addresses higher than 100 are supported by the system but will not
report.

3.2 General Settings 2

Primary:
Primary Format: Select SIA, 4+2 standard*, or Ademco Contact ID.
Primary Phone Number: Enter the primary phone number. The phone number may be preceded by one or more command codes.
See the description of the "Additional Phone Commands" field below.
Primary Account Code: Enter the vendor account code for the primary phone number. The field for 4+2 Standard and Ademco
Contact ID accommodates four digits. The field for SIA accommodates six digits.
Primary Test Time Interval: Select 4, 6, 8, 12, or 24 for automatic test report transmission to the primary phone number every 4, 6,
8, 12, or 24 hours.
Note that if the primary and secondary test times are different, the first test message will select the primary line. The next test message will select the secondary
phone line. The line selection will continue to alternate in this manner.
If the primary and secondary test times are the same, the secondary line will be used for both messages and no alternation will occur.
NOTE: Test time intervals exceeding 6 hours do not comply with UL 864 10th Edition.
24
CAUTION:
THE START ADDRESS MUST EQUAL THE HOST'S UDACT-2 ACS ADDRESS.
Figure 3.2 General Settings 2 Screen
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019
General Settings 2