4 — Installation with the HONEYWELL STT700
The person with knowledge of safety operations will be required to do the installation and
operation. No special installation is required in addition to the standard installation practices
outlined in the STT700 Smart Transmitter User Manual. However please note that when the
device is in safety operation that the optional write protect must be set in software so that the
device is write protected and HART
device is in safety operation that the Latching and Break Detect parameters must be enabled.
See STT700 Smart Transmitter User Manuals for details concerning these parameters
The software write protect is also available in the device with a password to disable the software
write protect. The default password is "0000". It can be enabled / disabled through HART host.
IEC 61508 Ed. 2.0 compliant hardware/software revisions for the STT700 can be found in the
Exida and TÜV Certification Reports. In addition, the most recent release information can be
found in the following document:
https://www.honeywellprocess.com/library/support/Public/Downloads/SmartLineHARTTemperat
ureFirmwareRevisions.zip

Parameter settings

The following parameters need to be set in order to maintain the designed safety integrity:
mA Fault action
(Upscale/Downscale)
Engineering Range
4
®
devices must be disconnected. Also note that when the
The transmitter is shipped with a default failsafe
direction of upscale (21.5 mA.). This is acceptable
for all high trip applications. For low trip
applications, the fail-safe direction is downscale
(3.58 mA.). Transmitter configuration for burnout
operation may be changed from Host (DD/DTM) to
accomplish this action, see the User Manual.
All engineering range parameters must be entered
to match the trip points in the safety logic solver.
These parameters must be verified during the
installation and commissioning to ensure that the
correct parameters are set in the transmitter.
STT700 Safety Manual
June 2017