1.4 Description

The Universal Digital Alarm Communicator/Transmitter (UDACT-2) may be used with a variety of control panels. The UDACT-2 trans-
mits system status to UL Listed Central Station Receivers, using modular jacks to interface primary and secondary phone lines to the
public switched telephone network. The UDACT-2, which is compact in size, mounts internally in some panels or externally in a sepa-
rate enclosure. EIA-485 annunciator communications bus and 24 volt (nominal) connections are required. Install HWF2A-COM or
HWF2V-COM IP Digital communicators alongside the UDACT-2 to provide a secondary transmission path in lieu of a second phone
line, per UL 864 10th edition requirements (41.3.2.9). The UDACT-2 is compatible with the following panels and network annunciators:
NOTE: Only one UDACT-2 can be installed on a host's EIA-485 ACS circuit.
Panel or
Network
Annunciator
For current and compatible firmware, log onto www.notifier.com and visit the Resources tab.

1.5 Features

Dual telephone lines.
Dual telephone line voltage detection.
Digital Communicator provides:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Dial tone recognition - 440 hertz tone typical in most networks
• Central Station number(s) dialing, Touch-Tone
• Protocols: SIA, 4 + 2, Ademco Contact ID.
Programming created with VeriFire Tools, downloaded to UDACT-2 through USB port.
Manual test report function.
Manual master transmission clear function.
Compact in size: 6.75" x 4.25".
Mounts in the panel box or in a separate enclosure.
Communicates vital system status including:
– Independent zone/point alarm, trouble and supervisory
– Security, panel off-normal, NAC trouble
– AC (main) power loss (programmable report delay).
LED status indicators for power, EIA-485 loss, primary and secondary line seizure, line failure, lack of tone, kissoff,
communication failure, and manual test. (Refer to Table 1.3 on page 11 for a complete list.)
Relay driver for Total Communication Failure or UDACT-2 trouble.
Real Time Clock keeps time for up to 48 hours when the UDACT-2 is unpowered. (UDACT-2 must be powered for 24 hours or
longer to ensure the 48 hours. Handling or moving the unit may discharge it faster.)
Simple EIA-485 interface to host panel.
Up to 14 point trouble messages transmitted per hour.

1.6 Specifications

1.6.1 DC Power - TB1
Requires 24VDC (nominal) regulated, non-resettable and power-limited power. Supervised.
52 mA in standby, 72 mA maximum while communicating and 87 mA with the output engaged and communicating.
12-18 AWG - wire must be sized for a voltage drop of no more than two volts.
8
• NFS2-3030
• NFS2-640
• NFS-320
• NCA-2
• AM2020/AFP-1010
• AFP-300/400
UDACT-2
EIA-485
Protected Premises
Figure 1.1 Block Diagram of a UDACT-2 Setup
• NFS-3030
• NFS-640
• AFP-200
• NCA
• NFS-320SYS
Public Switched
Telephone Network Lines
®
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019
Printer or monitor
Receiver
Receiver
Printer or monitor
Central Station(s)