Usb Port - J6; Ul Power-Limited Wiring Requirements - Honeywell NOTIFIER UDACT-2 Instruction Manual

Universal digital alarm communicator
Table of Contents

Advertisement

Installation and Wiring

2.7 USB Port - J6

The UDACT-2's USB port (J6) provides a USB Type B connection
for a computer running VeriFire Tools for UDACT-2 program-
ming.

2.8 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at
least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower-lim-
ited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
22
Telephone Connections
Nonpower-limited circuits
Power-limited circuits
Figure 2.19 Typical Wiring for UL Power-limited Requirements
UDACT-2
Figure 2.18 USB Port, J6
Use power-limited source
Power-limited circuits
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019
USB Port - J6
J6 - USB
Type B
connection

Hide quick links: