Honeywell NOTIFIER UDACT-2 Instruction Manual page 30

Universal digital alarm communicator
Table of Contents

Advertisement

Reporting Formats
• 3 = New Restore
XYZ = Event code. Refer to Table 5.2 for event code definitions.
GG = Group number. Zeroes, or the value defined in VeriFire Tools programming. (Refer to page 24.)
CCC = Device or Zone number.
• If the report concerns a specific point or zone, this field contains the UDACT-2 address of the device or zone. (See the
description of the "Point Address at Central Station" field on page 27).
• If the report is general (i.e., not a report concerning a specific point or zone) this field will display zeroes, or the value defined in
VeriFire Tools programming. (Refer to page 24.)
NOTE: For general reports (alarm, trouble and supervisory), the GG and CCC fields are transmitted as 00 and 000 unless values are
entered in the VeriFire Tools "Group" and "General Points Device Number" fields. (Refer to page 24.)
30
Data Description
General Alarm
Zone/point Alarm
General Supervisory
Zone/point Supervisory
General Fault
AC Fault
Zone/point Fault
Low Battery
Telco Primary Line Fault
Telco Secondary Line Fault
NAC Fault
Communication Trouble Primary #
Communication Trouble Secondary #
485 Communication Trouble
System Off Normal
Reserved
System 24 Hour Test
System 24 Hour Test with Active Event
Manual Test
Security Alarm
Future Use
Future Use
Future Use
Zone/point defined as fire alarm
Disable zone/point report
Zone/point defined as supervisory
Zone/point defined as pull station
Zone/point defined as heat detector
Zone/point defined as water flow
Zone/point defined as duct detector
Zone/point defined as pre-alarm
Zone/point defined as smoke
Zone/point defined as burglary
Zone/point defined as 24 hour non-burglary
Zone/point defined as high temperature
Zone/point defined as low temperature
Zone/point defined as low water pressure
Zone/point defined as low water level
Zone/point defined as pump failure
Zone/point defined as photo-co detector
* Factory default, reprogrammable.
Note: Zero event entries prevent the transmission of the report to the Central Station.
Table 5.2 Ademco Contact ID Reporting Format
Event Code
110*
110*
200
200
300
301
380
302
351
352
321
354
354
300
308
000
602
608
601
130
310
394
393
110
000
200
115
114
113
116
118
111
130
150
158
159
201
204
206
162
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019