Channel Test - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

8 LOCAL USER INTERFACE
If YES is chosen, the outputs are enabled, the status LED may turn GREEN (if disabling outputs or relay test was the cause
to turn it RED), and the ACT command menu is displayed. If NO is chosen, the outputs remain disabled, the status LED
stays RED and the ACT command menu is displayed. If any other key is pressed, an error message is generated and
[CLR] key must be pressed to clear the message.
The available ALPS tests and their corresponding numbers are:
1: End Test Mode
2: ZONE 1 AG
3: ZONE 1 BG
4: ZONE 1 CG
5: ZONE 2 AG
6: ZONE 2 BG
7: ZONE 2 CG
8: ZONE 3 AG
9: ZONE 3 BG
10: ZONE 3 CG
11: ZONE 4 AG
12: ZONE 4 BG
13: ZONE 4 CG
14: ANY Z1 GND
15: ANY Z2 GND
16: ANY Z3 GND
This command is used to allow the user to key (turn on) the local transmitter when a channel scheme (POTT1, POTT2,
PUTT, BLOCKING, or HYBRIDP) is used. Protection must be enabled to perform a channel test. If protection is disabled
when channel test is selected, the relay will prompt the user to enable protection.
If the [3/N] (NO) key is pressed, CANCELED is displayed and the test canceled. If the [1/Y] (YES) key is pressed, the relay
checks the outputs. If they are enabled, the test item is displayed. If the outputs are disabled, the user is prompted to
enable them. If the user responds with [3/N] (NO), CANCELED is displayed and the test is canceled. If the user responds
[1/Y] (YES), the outputs are enabled and the test item is displayed.
If 2. Channel test is selected, the privilege level must be CONTROL or MASTER and communications must not be per-
forming an action. If either check fails, an error message is displayed and the test is not performed. The error message
must be cleared by pressing the [CLR] key. When the checks pass and the test is started, the word ON will be displayed to
the right of the item.
When the user selects 1. End Chnl Test, the test is terminated and the user is returned to the Actions menu.
GE Power Management
17: ANY Z4 GND
18: ZONE 1 AB
19: ZONE 1 BC
20: ZONE 1 CA
21: ZONE 2 AB
22: ZONE 2 BC
23: ZONE 2 CA
24: ZONE 3 AB
25: ZONE 3 BC
26: ZONE 3 CA
27: ZONE 4 AB
28: ZONE 4 BC
29: ZONE 4 CA
30: ANY Z1 PHASE
31: ANY Z2 PHASE
32: ANY Z3 PHASE

CHANNEL TEST

Enable Protection?
CHANNEL TEST
1.End Chnl Test
2.Channel Test
CHANNEL TEST
1.End Chnl Test
2.Channel Test ON
ALPS Advanced Line Protection System
8.1 INTRODUCTION
33: ANY Z4 PHASE
34: IT DETECTOR
35: IB DETECTOR
36: GRD DIR TRIP
37: GRD DIR BLOCK
38: FAULT DETECTOR
39: REM OP DETCT
40: OUT OF STEP BLK
41: V1 DETECTOR
42: LINE OVERLOAD
43: INST PHS OVRC
44: INST GND OVRC
45: LINE PICKUP
46: OVER VOLTAGE
47: UNDER VOLTAGE
48:OUT OF STEP TRIP
8.1.17 CHANNEL TEST
8