Introduction - GE ALPS Instruction Manual

Advanced line protection system
Table of Contents

Advertisement

1 PRODUCT DESCRIPTION
1.3 CUSTOM PROGRAMMABILITY
The ALPS offers a high degree of custom programmability. Custom programming of the ALPS is accomplished using
Xpression Builder. Xpression Builder is a Windows based program that allows the user to design programmable logic and
make I/O (Input/Output) assignments for the ALPS and other GE Power Management relays. Xpression Builder is included
with ALPS software suite on the GE Power Management CD. A complete description of Xpression Builder is included in
Chapter 13: XPRESSION BUILDER.
In addition to the pre-programmed line protection schemes and configurable I/O, the ALPS relay includes the capability for
the user to design custom logic. This logic may be used to supplement or to replace the built-in scheme logic. The program-
mable logic includes the following: up to 40 logic gates (AND, OR, NOT), each with up to 4 inputs; 8 programmable timers
each with a settable pickup and dropout delay; 8 counters; and 8 latches.
All of the contact converters (Digital Inputs) in the ALPS are user configurable. However, each ALPS relay is shipped with
Default Contact Converter Assignments as shown below and on the default elementary diagrams on pages 1–49 to 1–52.
Each configurable input can be assigned only one flag – assigning more than one flag to a configurable
input may cause maloperation!
WARNING
Table 1–3: ALPS DEFAULT CONTACT CONVERTER ASSIGNMENTS: SINGLE PHASE MODEL
INPUT
DESCRIPTION
CC1
RECEIVER #1
CC2
RECEIVER #2
CC3
EXTERNAL STOP CARRIER
CC4
BLOCK PILOT TRIPPING
CC5
ENABLE THREE PHASE TRIPPING
CC6
REMOTE TARGET RESET
CC7
BKR 1 52b PHASE A
CC8
BKR 1 52b PHASE B
CC9
BKR 1 52b PHASE C
CC10
BKR 2 52b PHASE A
CC11
BKR 2 52b PHASE B
CC12
BKR 2 52b PHASE C
Table 1–4: ALPS DEFAULT CONTACT CONVERTER ASSIGNMENTS: THREE PHASE MODEL
INPUT
DESCRIPTION
CC1
RECEIVER #1
CC2
RECEIVER #2
CC3
EXTERNAL STOP CARRIER
CC4
BLOCK PILOT TRIPPING
CC5
CC6
CC7
BKR 1 52B
CC8
BKR 2 52B
GE Power Management
MNEMONIC
RCVR1
RCVR2
STCR
BLPTRP
ETRP3P
RESET
52B_1A
52B_1B
52B_1C
52B_2A
52B_2B
52B_2C
MNEMONIC
RCVR1
RCVR2
STCR
BLPTRP
52B_1
52B_2
ALPS Advanced Line Protection System
1.3 CUSTOM PROGRAMMABILITY
1.3.2 PROGRAMMABLE LOGIC
1.3.3 CONFIGURABLE INPUTS
INDEX #
NOTE
12
13
(if used)
10
(Blocking Scheme Only)
11
(Blocking Scheme Only)
7
20
1
2
3
4
5
6
INDEX #
NOTE
12
13
(if used)
10
(Blocking Scheme Only)
11
(Blocking Scheme Only)
1
4

1.3.1 INTRODUCTION

1
1-9