2.5 REFERENCE TABLES
Table 2–12: GENERAL SETTINGS GUIDE (Sheet 1 of 2)
NO.
MNEMONIC
CONFIGURE
101
UNITID
2
102
SYSFREQ
103
PHASROTATE
104
TIMESYNCH
105
NUM_BKR
106
NUM_TC
107
NUM_MON
108
DISPLAYVAL
109
LANGUAGE
110
SYSIN1-4
COMMPORTS
201
COMPORT1
202
COMPORT2
203
COMPORT3
204
PROTOCOL1
205
PROTOCOL2
206
PROTOCOL3
OSC_GRAPHY
301
NUMFAULTS
302
PREFAULT
303
SPLITREC
BRKR DUTY
401
EXPONENT
402
MAX_OP
† Applicable to the Single Phase Tripping model only.
‡ Applicable to the Three Phase Tripping model only.
* Contact converter output normally appears as a Logic 1 with normally open contact connected; to invert output to Logic 0, add 1000 to
the number.
2-64
DESCRIPTION
Unit ID
System Frequency
Phase Rotation
Time Synch Source
Number of Breakers
Number of Trip Circuits
Number of Trip Circuit Monitors
Value Display Mode
Language Option
System Inputs 1 to 4
Communications Port #1
Settings
Communications Port #2
Settings
Communications Port #3
Settings
Communications Port #1
Protocol
Communications Port #2
Protocol
Communications Port #3
Protocol
Number of Fault Records
Number of Pre-fault Cycles
Splits Fault Record and
captures this percentage at end,
with 1-SPLITREC captured at
beginning
x
Exponent in I
t calculation
Maximum Number of Breaker
Operations for a Breaker
ALPS Advanced Line Protection System
2 CALCULATION OF SETTINGS

2.5.3 GENERAL SETTINGS GUIDE

RANGE
STEP
(5A & 1A)
0000 to 9999
1
50 Hz, 60 Hz
N/A
ABC, ACB
N/A
INTERNAL, IRIG-B
N/A
1, 2
N/A
1, 2
N/A
for 1P tripping:
a-f = 0 (on) or 1(off)
format = abcdef;
for 3P tripping:
format = abcd
PRI, SEC
N/A
ENGLISH, SPANISH
N/A
0000 to 1111 (binary)
1
0 to 15 (decimal)
Baud Rate (xx), Parity
xx = 03, 12, 24, 48, 96;
(y), Stop Bits (z)
y = 0 (none), 1 (odd), 2
format = xxyz
(even);
z = 1, 2
Interface (i), Baud Rate
i = 0 (RS232), 1
(xx), Parity (y), Stop Bits
(RS485); xx = 03, 12,
(z)
24, 48, 96; y = 0
format = ixxyz
(none), 1 (odd), 2
(even);
z = 1, 2
Interface (i), Baud Rate
i = 0 (RS232), 1
(xx), Parity (y), Stop bits
(RS485); xx = 03, 12,
(z)
24, 48, 96; y = 0
format = ixxyz
(none), 1 (odd), 2
(even);
z = 1, 2
GE-MODEM, ASCII,
N/A
DNP 3.0
GE-MODEM, ASCII,
N/A
DNP 3.0
GE-MODEM, ASCII,
N/A
DNP 3.0
2,4,8,12
N/A
(std. mem.)
6,12,24,36
(exp mem)
1 to 8
1
0 to 100%
1
1.0 to 2.0
0.1
0 to 9999
1
DEFAULT
0000
60Hz
ABC
INTERNAL
1
1
000111 (7)
T1 to T3 off
0000 (0)
T1 to T4 off
SEC
ENGLISH
0000
9601
09601
09601
GE-MODEM
ASCII
GE-MODEM
12
5
0
2.0
0