Time And Date - Honeywell Touchpoint 1 Technical Manual

Single channel gas detector controller
Table of Contents

Advertisement

9
Alarm 2 settings are changed in the same way as for Alarm 1.
A2 alarm levels can be set between the A1 alarm level and the full scale range.
The default setting is 50% of the full scale range.
10
Press OK to accept the changes.
The display now changes to the F Fault Relay settings.
11
Fault Relay settings are changed in the same way as for the alarm relays.
12
Press OK.
The display returns to the menu selection screen.
13
Press Cancel.
Returns controller to normal operation.

Time and Date

This menu sets the controller's real-time clock.
1
Access the menu system and select the
Press Up or Down. The icon flashes.
2
Press OK.
At the bottom of the display the current selected year flashes.
3
Use Up/Down to change the year.
Between 2002 and 2099.
4
Press the OK button to accept the change.
The display changes to a flashing display of the current month
setting.
5
Use Up/Down to change the month.
Between 1 and 12.
6
Press OK to accept the change.
The display changes to a flashing display of the current day.
7
Use Up/Down to change the day.
Between 1 and 31.
8
Press OK to accept the change.
The display changes to a flashing display of the current time (hours).
9
Use Up/Down to change the hours.
Between 00 and 23.
TP1MAN Issue 3 Apr 06 (MAN0630)
menu option.
User Settings
44