7.9 Application settings

In table 7.4 the recommended parameter settings for different applications are
described.
Table 7.4: Application settings
Centrifugal fan
10 s
Axial fan
10 s
Centrifugal
10 s
pump
High pressure
10 s
pump
Compressor
5 s
Grinder
10 s
Mixer
10 s
Bow thruster
10 s
Hydraulic pump
10 s
10 s
Crusher
Conveyor belt
10 s
Escalator
10 s
Lift/Elevator
10 s
Cutter
10 s
Band saw
10 s
Circular saw
10 s
Please note that the parameter values above are to be used as a guide only. Variations in load
conditions may require additional tuning.
For Heavy Duty applications the Initial/End Voltage
might need to be increased.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Recommended basic setting
OFF
40 %
5.0 x I e
OFF
40 %
5.0 x I e
10 s
40 %
5.0 x I e
10 s
50 %
5.5 x I e
OFF
40 %
4.5 x I e
OFF
40 %
5.0 x I e
OFF
40 %
5.0 x I e
OFF
40 %
4.5 x I e
OFF
40 %
4.5 x I e
OFF
40 %
5.0 x I e
OFF
50 %
5.0 x I e
OFF
40 %
4.5 x I e
OFF
40 %
4.5 x I e
OFF
40 %
5.0 x I e
OFF
40 %
5.0 x I e
OFF
40 %
5.0 x I e
as well as the Current Limit
OFF
OFF
OFF
OFF
OFF
On
OFF
On
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Chapter 7