Connection Of The Operational Power Circuit - ABB PSE 18 Installation And Commissioning Manual

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

5L3
3L2
1L1
Figure 5.3: PSE18...PSE105 connection of the connection
module line side and motor side terminals
PSE18...105
1L1
3L2
2T1
4T2 6T3
PSE142...170
1L1
3L2
2T1
4T2 6T3
PSE210...370
1L1
3L2
2T1
4T2 6T3
Figure 5.5: Tightening torques and dimensions for terminal bars and lugs
34
Chapter 5
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201

5.2.3 Connection of the operational power circuit

The softstarter is recommended to be connected with a line contactor as de-
scribed in figure 5.1. Additional circuit diagrams will be found in Chapter 11 Wiring
diagrams.
Softstarters PSE18...PSE105 are provided with built-in cable clamps. The cables
must be stripped before connection, and the length of the exposed wire should
be 20 mm or 0.8 in. Connect according to figures 5.3 and 5.5.
For Softstarters PSE142...PSE370 the cables must have lugs and be connected
to the terminal bars, according to figure 5.4 and 5.5.
Connect the line side to terminals 1L1, 3L2, 5L3.
Connect the motor to terminals 2T1, 4T2, 6T3.
The terminals marking are printed on the front of the softstarter.
Using connection module
5L3
AWG12 .. 6
2,5 .. 10 mm
M8
2x2,5 .. 2x10 mm
AWG6 .. 2/0
10 .. 70 mm
2x10 .. 2x70 mm
Cu 75°C only
11/6-16 UNF-2S
5L3
275 lb.in
3/4-16 UNF-2A
5L3
375 lb.in
Warning!
Capacitors for power factor compensation are not allowed between the
softstarter and the motor, since this can cause current peaks which can
burn the thyristors in the softstarter. If such capacitors are to be used, they
should be connected on the line side of the softstarter.
3L2
1L1
Figure 5.4: PSE142...PSE370 connection of the line side and
motor side terminals
}
2
6 Nm - 53 lb.in
2
M6
}
2
8 Nm - 71 lb.in
9 Nm - 80 lb.in
2
Using connection module
M8
ATK185: AWG4 to 300kcmil
Cu 75°C only
18 Nm - 160 lb.in
Using connection module
ATK300: AWG4 to 400kcmil
M10
ATK300/2: AWG4 to 500kcmil or
2xAWG4 to 2x500kcmil
28 Nm - 240 lb.in
Cu 75°C only
5L3
Using connection bars
(If connection module is removed)
max
22 mm
(0.866 in)
Using connection bars
max
24 mm
(0.945 in)
Using connection bars
max
30 mm
(1.181 in)
2T1 4T2 6T3
max
20 mm
(0.787 in)
max
5 mm
(0.197 in)
max
22 mm
(0.866 in)
max
8 mm
(0.315 in)
max
30 mm
(1.181 in)
max
10 mm
(0.394 in)