Figure 5.10: Terminals for start and stop, conventional
circuit with push button
1
2
3
Figure 5.12: Tightening torques and wire area
5.2.4.3 Start and Stop, terminals 8 and 9 in circuit with terminals 11
or 12.
The PSE Softstarter has a built-in holding circuit and does not require sustained
signals on start input. Use internal control supply voltage from terminals 11 or 12.
Connection of start and stop terminals using conventional circuit with push but-
tons, see figures 5.10 and 5.12.
A conventional circuit with auxiliary relay is also possible, see figure 5.11 and 5.12.
Warning!
Do not connect an external voltage to any of the control terminals 8, 9, 10,
11, 12 and 13. Failure to observe the above may damage the softstarter and
the warranty may no longer be valid.
Start
Stop
7
8
9 10 11 12 13 14
PSE 18-600-70
4
5
6
7
8 9 10 11 12 13
14
0,5 Nm - 4,3 lb.in
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
1
2
3
4
Figure 5.11: Terminals for start and stop, conventional
circuit with auxiliary relay
3,5 x 0,6 mm
M3
(0.138 x 0.024 in)
5
6
7
8
9 10 11 12 13 14
PSE 18-600-70
AWG 24 ... 12
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
L
Stop
Start
N
Chapter 5
37