Fault Indications - ABB PSE 18 Installation And Commissioning Manual

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

Status
Software fault
Red Fault LED steady lighting or flashing,
and LCD event code SF20.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
Shunt fault
Red Fault LED steady lighting, and LCD
1
event code SF3x
.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
By-pass open
Red Fault LED steady lighting, and LCD
event code SF4x
1
.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
Softstarter thermal overload
Red Fault LED steady lighting, and LCD
event code SF50.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
SF = Softstarter fault
EF = External fault
P = Protection
x = phase number, 4 indicates multiple or unknown phase
1

10.6 Fault indications

Possible cause
Fault in software.
PSE parameter fault.
Fault
By-pass relays closed after transport,
(PSE18...PSE170 only).
Fault
The by-pass contactor's/relays are not
opening.
Thyristors short circuit.
Power loss on control supply circuit.
By-pass relays/contactor's open or by-
pass relays/contactor's do not close.
Fault
Thyristors overheated. If the fault remains
after reset, the heat sink temperature is too
high.
Fault
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Solution
Disconnect and reconnect the control
supply voltage (U s ) and make a re-
start. See chapter 5.2.4.
If same fault remains, contact your
ABB Sales Office.
Check parameter PSE and select cor-
rect setting corresponding to the type
of PSE Softstarter. See chapter 7.7.2.
Switch off operational voltage and
control supply voltage. Switch on volt-
age in correct succession.
1. Control supply voltage on terminals
1 and 2. See chapter 5.2.4.
2. Wait 4 seconds, and then switching
on operational voltage on terminals
L1, L2 and L3. See chapter 5.2.3.
Check and replace relay. Contact your
ABB Sales Office for replacement kit.
Check and replace thyristor. Contact
your ABB Sales Office for replacement
kit.
Check control supply voltage
Check and replace by-pass relay/con-
tactor. Contact your ABB Sales Office
for replacement kit.
Check that the fans are working in a
proper way. See chapter 9.1.
Check that the cooling airways are
free from dirt and dust. See chapter
9.1.
Check that the ambient temperature
is not too high. Derating is required
above 40
C (104
F). See chapter 3.6.
o
o
Check that the mounting angle is not
more than 30
. See chapter 4.2.4.
o
Check that PSE Softstarter not is too
small for the number of starts and
stops performed each hour.
Chapter 10
89