Status
Transfer of parameters failed
Only showing on external keypad. Can
occur for transfer both from the PSE and
to the PSE. Same failure for F1, F2, F3, F4
and F6.
Ready
Run
Protection
Transfer of parameters failed
Only showing on external keypad. Can
occur for transfer to the PSE.
Ready
Run
Protection
All parameters was not transferred
Only showing on external keypad. Can
occur for transfer both from the PSE and
to the PSE.
Ready
Run
Protection
Transfer of parameters failed
Only showing on external keypad. Can
occur for transfer to the PSE.
Ready
Run
Protection
10.8 Failure indications
Possible cause
Fault in software.
Fault
No parameters stored in the PSEEK.
Fault
Fault in software.
Fault
Not possible to transfer parameters to PSE
when it is in TOR.
Fault
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Solution
•
Try again.
•
If the same failure remains, contact
your local ABB Sales Office.
•
Load the parameters that you want to
transfer from selected PSE.
•
If the same failure remains, contact
your local ABB Sales Office.
•
Try again.
•
If the same failure remains, contact
your local ABB Sales Office.
•
Return the PSE to idle state and try
again
•
If the same failure remains, contact
your local ABB Sales Office.
Chapter 10
93