Single Transmitter Distances

For installations that have dedicated wiring between the transmitter and the
power supply, use the following chart. These distances assume stranded wire is
used.
Configuration
XNX mV or EC
With Sensor
XNX IR with
Searchpoint Optima Plus
XNX IR with
Searchline Excel
NOTE
If multiple transmitters are using the same power supply, make sure the
power supply wattage rating is high enough to power all transmitters
simultaneously.

Daisy-Chained Transmitter Distances

A few selected scenarios are presented here to provide a base to work from.
1. Several transmitters equally spaced from themselves and the power
source.
Configuration
XNX mV or EC
With Sensor
XNX IR with
Searchpoint Optima Plus
XNX IR with
Searchline Excel
XNX Universal Transmitter Quick Start Guide
Single Transmitter Distances
18 AWG
16 AWG
[1�0 mm
]
[1�5 mm
2
1140 feet
1810 feet
[347 meters]
[551 meters]
660 feet
1060 feet
[201 meters]
[323 meters]
550 feet
890 feet
[168 meters]
[270 meters]
2 Transmitters - Distance "d"
18 AWG
16 AWG
[1�0 mm
]
[1�5 mm
2
380 feet
600 feet
[115 meters]
[183 meters]
220 feet
350 feet
[67 meters]
[106 meters]
185 feet
295 feet
[56 meters]
[90 meters]
14 AWG
]
[2�0 mm
]
2
2
2890 feet
[880 meters]
1690 feet
[515 meters]
1410 feet
[430 meters]
14 AWG
]
[2�0 mm
]
2
2
960 feet
[292 meters]
560 feet
[170 meters]
470 feet
[143 meters]
12 AWG
[3�5 mm
]
2
4620 feet
[1408 meters]
2690 feet
[820 meters]
2260 feet
[690 meters]
12 AWG
[3�5 mm
]
2
1540 feet
[469 meters]
900 feet
[274 meters]
750 feet
[229 meters]
13