Honeywell stt850 SMARTLINE User Manual page 42

Temperature transmitter
Hide thumbs Also See for stt850 SMARTLINE:
Table of Contents

Advertisement

Match PVs (Dual
Inputs only)
(HART/FF only)
Latching
Device
Setup
CJ Source
Fixed CJ Value
<Return>
Disabled when Loop Control Mode is disabled
HART
Device ID
Setup
Universal Rev
(HART
Field Device Rev
only)
Final Assy Num
Loop mA
Poll Address
PV Units
SV Units
<Return>
Year # # # #
Month
HART Date
(HART
Day # #
only)
Write Date
Page 32
Enabled,
Disabled
Determines the source of the Cold Junction
compensation for Thermocouple Sensor types.
Valid range of -40 to +85°C. Out of Range warning
generated for temperatures between -45 and -50°C
and between +85 and +90°C. Suspect Input failure
generated for temperatures below -50°C and
above +90°C
Internal
External
Fixed
####.##
Unique for each device
HART Revision
For DD/DTM compatibility
Asset tracking number
Disabled for Multidrop
0 (default) to 63
Units of transmitted PV
Units of transmitted SV
Enter the current year
January through
December
Enter the day of the
month
Press ENTER to write
the HART Date to the
Transmitter
STT850 Temperature Transmitter User's Manual
Match PVs value for when Loop
Ctrl Mode is in Redundant mode
When enabled, causes all critical
sensor input failures to latch to the
Critical Fault state. The fault may
only be cleared by device reset.
When disabled, the critical sensor
input failure will be cleared if the
input recovers.
Uses internal CJ sensor.
Uses a Pt100 RTD on Input 2 as
the CJ source.
User configurable value for CJ
temperature.
When CJ Type is Fixed, specifies
the Cold Junction temperature
value for thermocouple Sensor
types. Degrees Celsius. Range of
-50.0°C to 90.0°C
Select the current
month
Select the current day
Press  to
enter menu
selection
 and  to
select
Alphanumeric
 to enter
and shift to
next
character to
the right.
Read Only
Read Only
Read Only
Revision 3