Table 10 -Transmitter Setup Menus - Honeywell stt850 SMARTLINE User Manual

Temperature transmitter
Hide thumbs Also See for stt850 SMARTLINE:
Table of Contents

Advertisement

<Return> Return to the Level 1 menu
<Return>
Tag ID
(HART/DE only)
Damping (sec)
(HART/DE only)
NAMUR Output
(HART/DE only)
Loop Ctrl Mode
(Dual Inputs only)
(HART/DE only)
(Read only for DE)
Loop Ctrl Src
(HART only)
Device
Setup
Delta Limit
(Dual Inputs only)
(HART/FF only)
Bumpless Damping
(HART/FF only)
Hysteresis
(Dual Inputs only)
(HART/FF only)
Break Detect*
* Spurious readings may occur if Break Detect is off in delta mode
Revision 3
Table 10 –
Transmitter Setup Menus
##. #
Disabled
Enabled
Average,
Differential,
Sensor 1,
Sensor 2,
Split-Range,
Redundant
Sensor 1,
Sensor 2
####.##
##.#
###.##
Enable,
Disable
STT850 Temperature Transmitter User's Manual
Enter Tag ID name up to 8
characters long.
= any
Alphanumeric value
Selection applies digital filtering to
suppress noise effects on the PV.
The limits for this value are 0.0 to
32.0 seconds
Disabling sets the loop output and
burnout levels to the Honeywell
levels
Enabling sets the loop output and
burnout levels to the NAMUR
levels
Mode of Loop control
Input sensor currently controlling
the Loop
User can configure the Delta
Limit. If the Critical Excess Delta
Detection has also been enabled,
the critical fault will be set when
the PV Delta (Sensor 1-Sensor 2
value) exceeds the Delta Limit."
Damping value for the transition
of Loop Control between Sensors
when Loop Ctrl Mode is Split-
Range or Redundant
Hysteresis value relative to the
MRV for the transition of Loop
Control between Sensors when
Loop Ctrl Mode is Split-Range
When enabled, adds a constant
bias value to the Sensor 2
measured value to equate it to the
Sensor 1 measured value at the
moment selected.
Press  to
enter menu
selection
 and  to
select
Alphanumeric
 to enter
and shift to
next
character to
the right.
Page 31