30

Advanced RF communication check

!
To save power the
battery devices only
communicate with the
evohome Controller
every four minutes
therefore the system
may not respond
immediately to a manual
change.
Step 4: System test
To check the RF signal strength between the
wireless devices and the evohome Controller go
to RF COMMS CHECK in the evohome Controller
Installer Menu and test each wireless device.
On the evohome Controller press and
1
hold 'Settings' for 3 seconds
Press the green tick
2
Press RF COMMS CHECK
3
Choose the devices you want to test
4

Mains Powered Wireless Devices

Mains powered devices do not need to be put into
test mode and will automatically respond to the test
message sent from the evohome Controller:
Wireless Relay Box (BDR91)
• The Relay Box will flash the red LED from 1 flash (poor) to
5 flashes (excellent) – no flashing means the Relay Box has
not received a test signal from the evohome Controller
Underfloor Heating Controller (HCE80/HCC80)
• The Underfloor Heating Controller will flash the
green LED for the zone you are testing from 1 flash
(poor) to 5 flashes (excellent) – no flashing means
the Underfloor Heating Controller has not received
a test signal from the evohome Controller