Display Module Screen Operations; How Do I Set Lan Parameters; How Do I Check Temperature And Humidity Curves - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual

11.3 Display Module Screen Operations

11.3.1 How Do I Set LAN Parameters?

If the teamwork networking mode is FE networking, set the LAN parameters
based on the actual situation.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > LAN IP Settings, and
set LAN IP assigning mode to Manual. Set LAN IP address, LAN subnet mask,
and LAN gateway based on the actual plan.
Figure 11-11 LAN IP settings
----End

11.3.2 How Do I Check Temperature and Humidity Curves?

Context
On the T/H Curve screen, the temperature and humidity curves show the recent
temperature and humidify changes. You can choose to display the curves in recent
one hour, one day, seven days, or 30 days.
Issue 10 (2024-01-30)
NO TE
● If the LAN IP address of the unit has not been changed, the LAN IP address of each
unit in the group is reallocated when the Teamwork function is enabled.
● If the LAN IP address of the unit has been changed, the LAN IP address of the unit
remains unchanged when the Teamwork function is enabled.
● The LAN IP address must be in the 192.168.248.X network segment.
Copyright © Huawei Digital Power Technologies Co., Ltd.