5.4.3 (Optional) Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the units have been set as follows:
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen.
Figure 5-4 Teamwork Settings
Issue 10 (2024-01-30)
Description
Specifies the control type
for the indoor fan.
Specifies the measuring
range for the air-side
differential pressure
sensor.
Specifies the minimum
speed for the indoor fan.
Specifies the maximum
speed for the indoor fan.
Teamwork group num: Group the units in same aisle or adjacent areas as one,
that is, assign one teamwork group number for them. At most four teamwork
groups can be assigned (1–4).
System address: The address (configurable range: 1–32) of each unit in the
same group must be unique. The unit with the smallest unit address is the
master unit, which collects, processes, and delivers group data.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
5 Power-On and Commissioning
Configuration Principle
Normally, retain R/S air
temp diff rate ctrl. If
differential pressure sensors
are configured, change it to
Pressure diff ctrl.
There is no default value. Set
it to 0–500 Pa.
The default value is 30%.
You are advised to retain the
default value.
The default value is 100%.
99