Replacing A Liquid Level Switch - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Figure 10-9 Removing a drive
Step 7 Install the new drive.
Step 8 Connect the new drive cables.
Step 9 Close the No. 2 maintenance door.
Step 10 Power on the device.
Step 11 Tap Start on the home screen, choose Maintenance > Diagnostic Mode > Enter,
start the compressor, and check whether it works properly without any alarms.
Then exit the diagnostic mode.
----End

10.7 Replacing a Liquid Level Switch

Prerequisites
Context
The liquid level switch needs to be maintained from the outdoor air intake vent.
Issue 10 (2024-01-30)
A spare liquid level switch of the same model is available and functional.
Tool: solid wrench