5.4.2 (Optional) Setting the Pressure Difference Control

Prerequisites
If differential pressure sensors are installed, perform the following operations
accordingly. If differential pressure sensors are not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor Fan, and set
Air-side difference pressure sensor type to 0–500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change other parameters based on the following instructions.
Issue 10 (2024-01-30)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Lower Limit of
Humidity Setpoint (%
RH)
15
15
15
15
15
15
15
15
15
15
15
15
15
15
5 Power-On and Commissioning
Upper Limit of
Humidity Setpoint (%
RH)
47.3
44.7
42.2
40
37.8
35.8
33.9
32.1
30.5
28.9
27.4
26
24.7
23.4
98