Blind Function Selection = 1
Communication Parameters Blind = 1
Frequency Mode Selection = 3
Command Mode Selection = 3
Communication Parameters Group:
Communication Selection = 3
TOSLINE-S20 Receiving Address = 40
TOSLINE-S20 Sending Address = 0
TOSLINE-S20 Command Input = 3
TOSLINE-S20 Monitor Output = 31
TOSLINE-S20 Freq Ref Address Selection = 1
TOSLINE-S20 Freq Ref Address = 42
TOSLINE-S20 Com Err Mode = 0
TOSLINE-S20 Com Option Reset = 0
Sending and Reading Information (ie with MMI)
(using the addresses set in the continuous example)
S-20 Adr
W0000
W0001
W0002
W0003
W0004
W0040
W0041
W0042
W0043
W0044
From G3 to T2:
W0001 Actual Speed (multiplied by 1000, refer to command input)
From T2 to G3:
W0040 Command Word
(ie
bit 0: 0=stop / 1=run
bit 1: not used
bit 2: 0=forward / 1=reverse ... etc)
W0042 Speed Command Value (multiplied by 1000, refer to monitor output)
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
G3
status register
feedback speed
output current
excitation curr.
torque current
2192
T2
command (run)
speed ref.
aux speed
current limit
drooping gain
85