Pattern Run - Toshiba G3 Workbook

Applications workbook
Table of Contents

Advertisement

Introduction
Like the G2/G2+, the G3 has a Pattern Run feature. Pattern Run allows the user to associate a time, direction,
accel/decel time, and volts/hertz pattern with each preset speed. Any seven of the fifteen preset speeds can be
strung together to create a pattern; the G3 stores four such patterns. The number of times a pattern repeats is
programmable from one to infinity.
Pattern Run Diagram
Forward
30 Hz
ACC2 used
15 Hz
Speed 1
time =
3 sec
11 Hz
ACC1 used
Reverse
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-

Pattern Run

Speed 2 time = 6 sec
time =
change in HZ /
Max Out Freq * ACC2
= 15/80*30 = 5.625sec
2192
DEC1 used
time
Speed 3
time =
3 sec
time=41/80*5 = 2.56 sec
3
8