Toshiba G3 Workbook page 84

Applications workbook
Table of Contents

Advertisement

Command Bit Table
When sending a command status to the G3 address, (ie W0040) use the following table:
bit
0
1
2
3
4 to 6
7
8
9
A
B
C
D
E
F
Command Input:
Speed Base Value
Auxiliary Speed Base
External Current Limit
Drooping Online Gain
Monitor Output:
Speed FeedBack Value
Output Current Value
Excitation Current Value
Torque Current Value
1
This will cause the displayed frequency to match the actual drive frequency.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
0
stop
not used (keep at 0)
reverse rotation
acc/dec #1
normal run
feedback available
no dc braking
VF1
run
run
reset trigger (turn to 1)
0 - 27500
Set max frequency (FH) to 275.
0 - 27500
FH as above; 110% = 27500
0 - 10200
Stall protect level; 100%= 4000
0 - 127
Drooping Control Value; 10% = 100
0 -27500
Max freq (FH); 110% = 27500
0 - 10200
Rated Current; 100% = 4000
0 - 10200
Rated Current; 100% = 4000
-128 to +127
Rated Current; 100% = +/- 4000
2192
1
run
normal rotation
acc/dec #2
not used
jog run
no feedback
dc braking
VF2
coast stop
emergency stop
not used
1