Bosch CL400 Manual page 75

Hide thumbs Also See for CL400:
Table of Contents

Advertisement

Bus Parameters
Backplane Module Display
1070 072 196-101 (00.06) GB
Via the B-button, the set bus parameters and an overview of the handled
data traffic are displayed.
Example:
COM-E name:
Ethernet address:
Internet address:
Retransmission counter:
Retr.Timer:
Subnet mask: 255.255.0.0
AstKmd:
00000527
Rep-AstKmd:
00000050
Arp:
00000009
Icmp:
00000001
IP:
001FE135
Rep-Ip:
0000002E
OverrunCnt:
00000000
AstKmd:
Number of executed client jobs
Rep-AstKmd:
Number of message repeats with these client jobs
Arp:
Number of received ARP request messages
Icmp:
Number of received ICMP requests (Ping)
IP:
Number of received client jobs
Rep-Ip:
Number of message repeats with the received client jobs
OverrunCnt:
Overruns in the Ethernet controller
Via the P-button, the modules that have been recognized in the card rack are
displayed.
Example:
VFD 0: ZS400
BlkAdr:
VFD 9: COM-E
BlkAdr:
VFD 0 to 9
Module number in the SK table
Module type
BlkAdr
Set block address of the module
Version
High byte = hardware version / Low byte = software version
Ethernet Job Listing
Control_1
00-60-34-00-08-0B
142.2.26.146
16
200
Constant retransmission
Default gateway 0.0.0.0
00F0 0000
Version
0024 0000
Version
9- -3
0025 stat
0410
0011 stat
0000

Hide quick links: