2- -14
Hardware
2.6

Configuration File

2.6.1

Keywords

With the configuration file, several presettings and default values on the
COM-E can be changed. The file is imported into the COM-E module using
the WinSPS editor, version 2.3 and higher, submenu 'Controls', via SK, ZS or
COM-E, where it is then filed in a non-volatile way.
The configuration file can be created with any kind of ASCII editor. The data
is checked during loading. The entries are oriented towards keywords, the
parameters are divided by TABs or spaces. The semicolon is used for desig-
nation of the start of a comment.
At the lower segment display, an "n" will appear if there is no configuration file
loaded.
.
The COM-E module is configurated in such a way that, in general, it is
not necessary to load a ProjDat.eth configuration file!
Not all keywords must be specified in the configuration file. In case of miss-
ing information, the corresponding default value is valid.
Keyword
Retransmissiontimer
Retransmissioncounter
Retransmissionmode
IP-Table
IP-Lifetime
Ethernet-Overwrite
Subnet-Mask
Default-Gateway
Password
Default Value
200 ms
16
0
; constant repeat time
120
; 120 seconds
0
; no overwrite
255.255.0.0
no default address
no password
1070 072 196-101 (00.06) GB