Mitsubishi Electric MELSEC Q Series User Manual page 431

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Return value
(HEX)
Memory card mount/unmount error
-260
• The SD memory card mounting process or un-mounting process has failed.
(FEFC
)
H
• The CompactFlash card mounting process or un-mounting process has failed.
-262
User CPU restarting error
(FEFA
)
• The user CPU is not ready for restarting.
H
-263
Call source flag error
(FEF9
)
• The value specified in the call source flag is out of range.
H
-264
Pointer error
(FEF8
)
• The specified pointer address is invalid.
H
-265
The target system specification error
(FEF7
)
• A value specified for the target system is out of range.
H
Watchdog timer startup error
-266
• User watchdog timer is started up by Setting/monitoring tools for the C Controller
(FEF6
)
H
module.
Error description
Corrective action
• Retry.
• Verify that the SD memory card or CompactFlash card is not damaged.
• Replace the SD memory card or CompactFlash card.
• Configure settings to permit user CPU restarting in Setting/monitoring
tools for the C Controller module.
• Check if the C Controller module is in STOP status.
Review the specified value, and specify a value that is within range.
Check the specified pointer.
Review the specified value, and specify a value that is within range.
Check the user watchdog timer setting.
(If user watchdog timer is started up by Setting/monitoring tools for the C
Controller module, the user watchdog timer cannot be started up or stopped
by the user program.)