State
Ready
DC link
Green / red
–
flashing light
0.5 Hz
Green / red
–
flashing light
2 Hz
Green /
–
orange
or
Red / orange
flashing light
5.2.2.6
Single Motor Module / Double Motor Module / Power Module
Table 5- 9
Meaning of the LEDs on the Motor Module
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
–
Green / red
–
flashing light
0.5 Hz
Green / red
–
flashing light
2 Hz
Green /
–
orange
or
Red / orange
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Description, cause
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messag-
es being reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
Diagnostics
5.2 Diagnostics using LEDs
Remedy
–
Carry out a POWER ON
–
Remedy
–
–
–
Check the line voltage
–
Remedy and acknowledge
fault
–
Carry out a POWER ON
–
145