Memory Validation Failed; State Exchange Voter Disagreement Detected; Nans Detected In Calc Or Nan_Breaker Block - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

352
Description Memory Validation Failed – Blockware Data Structures
Possible Cause A hardware memory failure because application process data was modified (data should not change after
controller goes online)
Solution Replace the controller.
353
Description Memory Validation Failed – Configuration Shared Memory
Possible Cause A hardware memory failure because system process data was modified (data should not change after
controller goes online)
Solution Replace the controller.
354
Description Memory Validation Failed – IONet Data Structures
Possible Cause There is a hardware memory failure because IONet process data was modified (data should not change
after the controller goes online)
Solution Replace the controller.
355
Description State Exchange Voter disagreement detected
Possible Cause
State Exchange disagreement found
Application sequencing error
IONet malfunction or hardware problem
Solution
Use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement.
In the application, avoid use of global variable 'ControllerID' and avoid the use of 'USB_HB' block.
Check IONet (switches, cables). If problem persists, replace the processor module.
356
Description NANs detected in CALC or NAN_BREAKER block
Possible Cause
NaN (Invalid floating point number) received from I/O interface
Hardware problem
Solution
Check for external devices that may be sending NaNs to the controller.
If conditions persists, replace the controller.
Controllers
Public Information
GEH-6855_Vol_II System Guide 55