I/O Pack In Stand Alone Mode; I/O Pack In Remote I/O Mode; Special User Mode Active - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

4
Description

I/O pack in stand alone mode

Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild the system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
5
Description

I/O pack in remote I/O mode

Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild the system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
6
Description
Special User Mode active. Now: [ ]
Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
444
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II